Original Version
Rule 92.1-A
92.1-A. Between Low Voltage Rack Conductors
and Other Conductors
On jointly used poles, the following minimum vertical clearances shall apply between 0-750 volt supply conductors in rack construction and other conductors (see App. G, Fig 9):
Racks above |
|
Conductors or cables 15’’ or more from center line of pole |
4 feet |
Unguarded cables, messengers or racks attached to poles |
6 feet |
Guarded cables, messengers, or racks attached to poles |
4 feet |
Unguarded racks below |
|
All circuits |
6 feet |
Guarded rack below |
|
Circuits of 0-21,000 volts or communication circuits |
4 feet |
Strikeout and Underline Version
Rule 92.1-A
92.1-A. Between Low Voltage Rack Conductors
and Other Conductors
On jointly used poles, the following minimum vertical clearances
shall apply between 0-750 volt supply conductors in rack construction and
other conductors (see App. G, Fig 9):
Racks above |
|
Conductors or cables 15’’ or more from center line of pole |
4 feet |
Unguarded cables, messengers or racks attached to poles |
6 feet |
Guarded cables, messengers, or racks attached to poles |
4 feet |
Unguarded racks below |
|
All circuits |
6 feet |
Guarded rack below |
|
Circuits of 0- |
4 feet |
Final Version
Rule 92.1-A
92.1-A. Between Low Voltage Rack Conductors
and Other Conductors
On jointly used poles, the following minimum vertical clearances shall apply between 0-750 volt supply conductors in rack construction and other conductors (see App. G, Fig 9 ):
Racks above |
|
Conductors or cables 15’’ or more from center line of pole |
4 feet |
Unguarded cables, messengers or racks attached to poles |
6 feet |
Guarded cables, messengers, or racks attached to poles |
4 feet |
Unguarded racks below |
|
All circuits |
6 feet |
Guarded rack below |
|
Circuits of 0-22,500 volts or communication circuits |
4 feet |