Rule 58.4-B3b


58.4-B3b)    From Conductors in Excess of 750 Volts Below: The vertical clearance of capacitor and regulator cases and their hangers from the level of conductors in excess of 750 volts below shall be not less than

 

12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-21,000 and
24 inches for conductors of21,000-35,000 volts.


Strikeout and Underline Version
Rule 58.4-B3b


58.4-B3b)    From Conductors in Excess of 750 Volts Below: The vertical clearance of capacitor and regulator cases and their hangers from the level of conductors in excess of 750 volts below shall be not less than

 

12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-
21,000 20,000 and
24 inches for conductors of 
21,00020,000-35,000 volts.


Final Version
Rule 58.4-B3b


58.4-B3b)    From Conductors in Excess of 750 Volts Below: The vertical clearance of capacitor and regulator cases and their hangers from the level of conductors in excess of 750 volts below shall be not less than

 

12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-20,000 and
24 inches for conductors of 20,000 -35,000 volts.