Original Version
Rule 86.4-C4b
86.4-C4b) Anchor Guys: Anchor guys which pass supply conductors
shall clear such conductors by not less than the clearances shown in Table
2, Case 19. Anchor guys which pass through the level of supply conductors
at positions other than between pole pin positions or outside of the outer
pin positions, shall be sectionalized by means of an insulator placed below
the supply conductors in accordance with the provisions of Rule 86.7-B, and
in addition thereto an insulator shall be placed not less than 2 feet
above the supply conductor level.
Strikeout and Underline Version
Rule 86.4-C4b
86.4-C4b) Anchor Guys: Anchor guys which pass supply conductors
shall clear such conductors by not less than the clearances shown in Table
2, Case 19. Anchor guys which pass through the level of supply conductors
at positions other than between pole pin positions or outside of the outer
pin positions, shall be sectionalized by means of an insulator placed below
the supply conductors in accordance with the provisions of Rule 86.7-B, and
in addition thereto an insulator shall be placed not less than 2 feet
above the supply conductor level.
The clearance between anchor guys and communication conductors
and/or cable attached directly to surface of pole, may be less than 3 inches
as specified in Table 2, Case 19, Column D, provided: The guy is not a ‘guy
in proximity’ or all parts of the guy are not less than 6 feet below 0-750-volt
supply conductors supported on same pole and a wood guard is placed on cable;
also, a guy attached to a pole which supports supply conductors at a distance
of not less than 6 feet above communication messenger and/or cable shall
(1) have an insulator placed in the guy at a distance of not less than 6
feet horizontally from the pole, or (2) have an insulator placed not less
than 3 inches nor more than 6 inches above the messenger and/or cable, and
a suitable wood guard placed on the messenger or cable.
Final Version
Rule 86.4-C4b
86.4-C4b) Anchor Guys: Anchor guys which pass supply conductors
shall clear such conductors by not less than the clearances shown in Table 2, Case 19. Anchor guys which pass
through the level of supply conductors at positions other than between pole pin
positions or outside of the outer pin positions, shall be sectionalized by
means of an insulator placed below the supply conductors in accordance with the
provisions of Rule 86.7-B, and
in addition thereto an insulator shall be placed not less than 2 feet
above the supply conductor level.
The clearance between anchor guys and communication conductors
and/or cable attached directly to surface of pole, may be less than 3 inches
as specified in Table 2, Case 19, Column D, provided: The guy is not a guy
in proximity’ or all parts of the guy are not less than 6 feet below 0-750-volt
supply conductors supported on same pole and a wood guard is placed on cable;
also, a guy attached to a pole which supports supply conductors at a distance
of not less than 6 feet above communication messenger and/or cable shall
(1) have an insulator placed in the guy at a distance of not less than 6
feet horizontally from the pole, or (2) have an insulator placed not less
than 3 inches nor more than 6 inches above the messenger and/or cable, and
a suitable wood guard placed on the messenger or cable.