Change List for this Rule

 

Original Version

Rule 84.6-D


84.6-D.    Vertical Runs

 

Vertical runs of communication wires or cables supported on the surface of wood poles or structures, shall be covered by a suitable protective covering (see Rule 22.2 ) where within a vertical distance of 3 feet above or 6 feet below unprotected supply conductors supported on the same pole or structure.  Vertical runs of communication wires or cables on the surface of a wood pole shall be covered by a suitable protective covering where within a 6-foot radius of any other pole supporting supply conductors except that those portions of such runs which are more than 3 feet above or 6 feet below the level of unprotected supply conductors need not be covered.  The plastic pipe specified in Rule 22.2-C shall have a minimum wall thickness of 0.15 inches.  Cable and drop wire runs to or from terminal boxes are excepted from these requirements for covering, under the following conditions:

 

Where guard arms are installed above messengers or longitudinal cables which are less than 6 feet below but not less than 4 feet below unprotected supply conductors of 0-750 volts, or where cables are supported on crossarms at not less than 15 inches from center line of pole, in which cases any portion of metal sheathed cable runs on the surface of pole below the guard arm and in the same quadrant as the longitudinal cable (see App. G, Fig. 86 ), or below and on the same side of the pole with a crossarm which supports a longitudinal cable, need not be covered.

Runs of bridled conductors, attached to surface of pole, need not be covered provided such runs are below the guard arm and in the same quadrant as the longitudinal cable, or where such runs are below and on the same side of pole with a cable arm and are not in the climbing space, or are connected to service drops which are placed in accordance with the provisions of Rule 84.8-B2b .

 

Where bridled runs are not required to be covered by these rules, they shall be supported by bridle hooks or rings spaced at intervals of not more than 24 inches.

Vertical runs shall be treated as risers (see Rule 84.6-E ) where within a distance of 8 feet from the ground line.

Runs which terminate in the top of enclosures which afford ample mechanical protection to the runs may extend within 8 feet of the ground but not less than 6 feet of the ground without being treated

 

Strikeout and Underline Version

Rule 84.6-D


84.6-D.    Vertical Runs

 

Vertical runs of communication wires or cables supported on the surface of wood poles or structures, shall be covered by a suitable protective covering (see Rule 22.2 ) where within a vertical distance of 3 feet above or 6 feet below unprotected supply conductors supported on the same pole or structure.  Vertical runs of communication wires or cables on the surface of a wood pole shall be covered by a suitable protective covering where within a 6-foot radius of any other pole supporting supply conductors except that those portions of such runs which are more than 3 feet above or 6 feet below the level of unprotected supply conductors need not be covered.  The plastic pipe specified in Rule 22.2-C shall have a minimum wall thickness of 0.15 inches.  Cable and drop wire runs to or from terminal boxes are excepted from these requirements for covering, under the following conditions:

 

Where guard arms are installed above messengers or longitudinal cables which are less than 6 feet below but not less than 4 feet below unprotected supply conductors of 0-750 volts, or where cables are supported on crossarms at not less than 15 inches from center line of pole, in which cases any portion of metal sheathed cable runs on the surface of pole below the guard arm and in the same quadrant as the longitudinal cable (see App. G, Fig. 86 87 ), or below and on the same side of the pole with a crossarm which supports a longitudinal cable, need not be covered.

Runs of bridled conductors, attached to surface of pole, need not be covered provided such runs are below the guard arm and in the same quadrant as the longitudinal cable, or where such runs are below and on the same side of pole with a cable arm and are not in the climbing space, or are connected to service drops which are placed in accordance with the provisions of Rule 84.8-B2b .

 

Where bridled runs are not required to be covered by these rules, they shall be supported by bridle hooks or rings spaced at intervals of not more than 24 inches.

Vertical runs shall be treated as risers (see Rule 84.6-E ) where within a distance of 8 feet from the ground line.

Runs which terminate in the top of enclosures which afford ample mechanical protection to the runs may extend within 8 feet of the ground but not less than 6 feet of the ground without being treated

 

Final Version

Rule 84.6-D


84.6-D.    Vertical Runs

 

Vertical runs of communication wires or cables supported on the surface of wood poles or structures, shall be covered by a suitable protective covering (see Rule 22.2 ) where within a vertical distance of 3 feet above or 6 feet below unprotected supply conductors supported on the same pole or structure.  Vertical runs of communication wires or cables on the surface of a wood pole shall be covered by a suitable protective covering where within a 6-foot radius of any other pole supporting supply conductors except that those portions of such runs which are more than 3 feet above or 6 feet below the level of unprotected supply conductors need not be covered.  The plastic pipe specified in Rule 22.2-C shall have a minimum wall thickness of 0.15 inches.  Cable and drop wire runs to or from terminal boxes are excepted from these requirements for covering, under the following conditions:

 

Where guard arms are installed above messengers or longitudinal cables which are less than 6 feet below but not less than 4 feet below unprotected supply conductors of 0-750 volts, or where cables are supported on crossarms at not less than 15 inches from center line of pole, in which cases any portion of metal sheathed cable runs on the surface of pole below the guard arm and in the same quadrant as the longitudinal cable (see App. G, Fig. 87 ), or below and on the same side of the pole with a crossarm which supports a longitudinal cable, need not be covered.

Runs of bridled conductors, attached to surface of pole, need not be covered provided such runs are below the guard arm and in the same quadrant as the longitudinal cable, or where such runs are below and on the same side of pole with a cable arm and are not in the climbing space, or are connected to service drops which are placed in accordance with the provisions of
Rule 84.8-B2b .

 

Where bridled runs are not required to be covered by these rules, they shall be supported by bridle hooks or rings spaced at intervals of not more than 24 inches.

Vertical runs shall be treated as risers (see
Rule 84.6-E ) where within a distance of 8 feet from the ground line.

Runs which terminate in the top of enclosures which afford ample mechanical protection to the runs may extend within 8 feet of the ground but not less than 6 feet of the ground without being treated