Original Version
Rule 54.4-D3
54.4-D3)
Conductors Passing and Unattached: The
centerline clearance between poles and conductors which pass unattached shall
not be less than 1 ½ times the clearances specified in Table 1, Case 8, except
where the interest pole is within 10 feet of a pole to which the passing
conductors are attached. Where poles of
the two lines are less than 10 feet apart, clearances not less than as
specified in Table 1, Case 8 shall be maintained between the center line of any
pole and conductors which pass unattached.
This rule will often necessitate
the use of clearance crossarms with conductor clearance as specified in Table
1, Case 8, or the alternate increased clearances for service drops as provided
in Rule 54.8-C3.
Strikeout and Underline Version
Rule 54.4-D3
54.4-D3)
Conductors Passing and Unattached: The
centerline clearance between poles and conductors which pass unattached shall
not be less than 1 ½ times the clearances specified in Table 1, Case 8, except
where the interest pole is within 10 feet of a pole to which the passing
conductors are attached or where the provisions of Table 1, Case 10, Columns
D, E, F, and G can be applied.
Where poles of the two lines are less than 10 feet apart, clearances not
less than as specified in Table 1, Case 8 shall be maintained between the
center line of any pole and conductors which pass unattached.
This rule will often necessitate
the use of clearance crossarms with conductor clearance as specified in Table
1, Case 8, or the alternate increased clearances for service drops as provided
in Rule 54.8-C3.
Final Version
Rule 54.4-D3
54.4-D3)
Conductors Passing and Unattached: The
centerline clearance between poles and conductors which pass unattached shall
not be less than 1 ½ times the clearances specified in Table 1, Case 8, except
where the interest pole is within 10 feet of a pole to which the passing
conductors are attached or where the provisions of Table 1, Case 10, Columns D,
E, F, and G can be applied. Where poles
of the two lines are less than 10 feet apart, clearances not less than as
specified in Table 1, Case 8 shall be maintained between the center line of any
pole and conductors which pass unattached.
This rule will often necessitate
the use of clearance crossarms with conductor clearance as specified in Table
1, Case 8, or the alternate increased clearances for service drops as provided
in Rule 54.8-C3.