Original Version
Rule 103.1-A
103.1-A. Splices and Taps
Splices shall not and taps should not be made in crossing
spans where Grade" A " construction is required. Splices and taps should
not be made in spans adjacent to such crossing spans if the crossing span
is not dead ended. Splices or taps in spans adjacent to a Grade" A " crossing
span shall, if practicable, be placed nearer to the crossing support than
the nearest conductor crossed over. This rule is not intended to prohibit
splices or taps on the free ends of conductors which are dead ended at the
crossing span.
The provisions of this rule shall not apply to conductor splices which are
made by any accepted standard method which has been proved by test before
the Railroad Commission to develop practically the full strength of the conductor
in which the splice is made.
Strikeout and Underline Version
Rule 103.1-A
103.1-A. Splices and Taps
Splices and taps should not be made in spans
adjacent to such crossing spans if the crossing span is not dead ended. Splices
or taps in spans adjacent to a Grade" A " crossing span shall, if practicable,
be placed nearer to the crossing support than the nearest conductor crossed
over. This rule is not intended to prohibit splices or taps on the free ends
of conductors which are dead ended at the crossing span.
The provisions of this rule shall not apply to conductor splices which are
made by any accepted standard method which has been proved by test before
the Railroad Commission to develop practically the full strength of the conductor
in which the splice is made.
(1) Splices shall not be made
or permitted in crossing spans where Grade “A” construction is required unless
the mutual consent of all parties involved in such spans is obtained.
Nothing contained in this Rule 103.1-A(1) shall be construed as requiring
that splices be made, or as granting authority for or permitting the making
of splices in such crossing spans without the consent of all parties owning
or operating overhead lines involved in such crossing spans.
(2) Splices and taps shall, as far as practicable, be avoided
in crossing spans where Grade “A” construction is required. If it is impracticable
to avoid such splices, they shall be of such type and be so made as to have
a strength practically equal to the conductor in which the splice is made.
Splices and tap should not be made in spans adjacent to such crossing spans
if the crossing span is not dead-ended. Splices or taps in spans adjacent
to a Grade “A” crossing span shall, if practical, be placed nearer to the
crossing support than the nearest conductor crossed over. This rule
is not intended to prohibit splices or taps on the free ends of conductors
which are dead-ended in the crossing span.
Final Version
Rule 103.1-A
103.1-A. Splices and Taps
(1) Splices shall not be
made or permitted in crossing spans where Grade “A” construction is required
unless the mutual consent of all parties involved in such spans is obtained.
Nothing contained in this Rule 103.1-A(1) shall be construed as requiring
that splices be made, or as granting authority for or permitting the making
of splices in such crossing spans without the consent of all parties owning
or operating overhead lines involved in such crossing spans.
(2) Splices and taps shall, as far as practicable, be avoided
in crossing spans where Grade “A” construction is required. If it is impracticable
to avoid such splices, they shall be of such type and be so made as to have
a strength practically equal to the conductor in which the splice is made.
Splices and tap should not be made in spans adjacent to such crossing spans
if the crossing span is not dead-ended. Splices or taps in spans adjacent
to a Grade “A” crossing span shall, if practical, be placed nearer to the
crossing support than the nearest conductor crossed over. This rule
is not intended to prohibit splices or taps on the free ends of conductors
which are dead-ended in the crossing span.