Rule 54.6-C2
54.6-C2) Conductors Of 0-750 Volts: Lateral conductors of 0-750 volts may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17, and with less than the clearance from center line and surface of pole, and from the surface of crossarm, as specified in Table 1, Cases 8 and 9, provided such conductors are suitably insulated and placed along the bottom surface of crossarms and are protected by wood moulding or impregnated fiber conduit of thicknesses not less than as specified in Rule 22.2, or are protected by plastic pipe designated as Type II, in the standard specified in Rule 22.2-C. The plastic pipe shall have a minimum wall thickness of 0.10 inches.
Strikeout and Underline Version
Rule 54.6-C2
54.6-C2)
Conductors
Of 0-750 Volts: Lateral conductors of 0-750 volts may be installed with less
than the radial clearances between conductors, specified in Table 2, Cases 16
and 17, and with less than the clearance from center line and surface of pole,
and from the surface of crossarm, as specified in Table 1, Cases 8 and 9,
provided such conductors are suitably insulated and placed along the bottom
surface of crossarms and are protected by wood moulding or impregnated fiber
conduit of thicknesses not less than as specified in Rule 22.2, or are
protected by plastic pipe having the properties and physical characteristics
specific for plastic pipe (Rule 22.2-C). designated as Type II, in the
standard specified in Rule 22.2-C. The plastic pipe shall have a minimum wall thickness of 0.10 inches.
Final Version
Rule 54.6-C2
54.6-C2) Conductors Of 0-750 Volts: Lateral conductors of 0-750 volts may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17, and with less than the clearance from center line and surface of pole, and from the surface of crossarm, as specified in Table 1, Cases 8 and 9, provided such conductors are suitably insulated and placed along the bottom surface of crossarms and are protected by wood moulding or impregnated fiber conduit of thicknesses not less than as specified in Rule 22.2, or are protected by plastic pipe having the properties and physical characteristics specific for plastic pipe (Rule 22.2-C).