Rule 57.4-G
57.4-G. From Buildings and Other Structures
Messengers and metal sheathed cables, which are bonded and grounded as specified in Rule 57.8 are not required to clear buildings and other structures any specified horizontal distance and the clearance specified in Table 1, Case 7, Column D does not apply in such instances. Such cables, and messengers, shall be installed so that they do not interfere with the free use of fire escapes, exits, etc., and shall be so arranged as to hamper and endanger workmen and firemen as little as possible in the performance of their duties.
Strikeout and Underline Version
Rule 57.4-G
57.4-G. From Buildings and Other Structures
Messengers and metal
sheathed cables, which are bonded and grounded as specified in Rule 57.8 are
not required to clear buildings and other structures any specified horizontal
distance and the clearance specified in Table 1, Case 7, Column D does not
apply in such instances. Such cables,
and messengers, shall be installed so that they do not interfere with the free
use of fire escapes, exits, etc., and shall be so arranged as to hamper and
endanger workmen and firemen as little as possible in the performance of their
duties. should be arranged so as not to hamper or endanger workers and
firefighters while performing their duties.
Final Version
Rule 57.4-G
57.4-G. From Buildings and Other Structures
Messengers and metal sheathed cables, which are bonded and grounded as specified in Rule 57.8 are not required to clear buildings and other structures any specified horizontal distance and the clearance specified in Table 1, Case 7, Column D does not apply in such instances. Such cables, and messengers, shall be installed so that they do not interfere with the free use of fire escapes, exits, etc., and should be arranged so as not to hamper or endanger workers and firefighters while performing their duties.