Original Version
Rule 84.6-B
84.6-B. Ground Wires
Ground wires, other than lightning protection wires not attached to equipment or ground wires on grounded structures, shall be covered by metal pipe or suitable covering of wood or metal or of plastic pipe material specified in Rule 22.2-C, for a distance above ground sufficient to protect against mechanical injury, but in no case shall such distance be less than 7 feet. Such covering may be omitted providing the ground wire in this 7-foot section has a mechanical strength at least equal to the strength of No.6 AWG medium-hard-drawn copper.
Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).
Strikeout and Underline Version
Rule 84.6-B
84.6-B. Ground Wires
Ground
wires, other than lightning protection wires not attached to equipment or
ground wires on grounded structures, shall be covered by metal pipe or suitable
covering of wood or metal or of plastic pipe conduit material
specified in Rule 22.2-CA, for a distance above ground sufficient
to protect against mechanical injury, but in no case shall such distance be
less than 7 feet. Such covering may be omitted providing the ground wire in
this 7-foot section has a mechanical strength at least equal to the strength of
No.6 AWG medium-hard-drawn copper.
Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).
Final Version
Rule 84.6-B
84.6-B. Ground Wires
Ground wires, other than lightning protection wires not attached to equipment or ground wires on grounded structures, shall be covered by metal pipe or suitable covering of wood or metal or of plastic conduit material specified in Rule 22.2-A, for a distance above ground sufficient to protect against mechanical injury, but in no case shall such distance be less than 7 feet. Such covering may be omitted providing the ground wire in this 7-foot section has a mechanical strength at least equal to the strength of No.6 AWG medium-hard-drawn copper.
Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).