Original Version
Rule 84.6-E
84.6-E.
Risers
Risers of wires or underground
cables shall be encased in securely grounded iron or steel pipe (or other
covering of equal strength) from the ground line to a level not less than 8
feet above the ground line. Risers from
underground cables of Class C circuits may be encased in plastic pipes or in
plastic U-shaped moulding, as provided in this rule, in lieu of the grounded
iron or steel pipe required by this rule. Such plastic pipe shall be of material as specified in Rule
22.2-C with a minimum nominal pipe size of 1 inch and with a minimum impact
strength equal to 2-½” nominal EPC-80-PVC plastic pipe.
Risers shall be covered by a
suitable protective covering as defined in Rule 22.2, where within a vertical
distance of 3 feet above or 6 feet below the level of unprotected supply
conductors supported on the same pole or structure.
Vertical risers where within both
a 6-foot radius of another pole supporting supply conductors and within a
vertical distance of 3 feet above or 6 feet below the level of any unprotected
supply conductor shall be covered.
Strikeout and Underline Version
Rule 84.6-E
84.6-E.
Risers
Risers of wires or underground
cables shall be covered encased in securely grounded iron or steel
pipe (or other covering of equal strength) from the ground line to a level
not less than 8 feet above the ground line. by one of the following:
(1)
Grounded (see definition 21.2) iron or
steel pipe, metal U-guard or other metallic covering of equal strength or;
Risers from underground cables
of Class C circuits may be encased in plastic pipes or in plastic U-shaped
moulding, as provided in this rule, in lieu of the grounded iron or steel pipe
required by this rule. Such plastic
pipe shall be of material as specified in Rule 22.2-C with a minimum nominal
pipe size of 1 inch and with a minimum impact strength equal to 2-½” nominal
EPC-80-PVC plastic pipe.
(2)
Conduit or U-shaped molding meeting the
requirements as specified in Rule 22.2.
Risers shall be covered by a
suitable protective covering as defined in Rule 22.2, where within for
a vertical distance of 3 feet above or to 6 feet below the level
of unprotected supply conductors supported on the same pole or structure.,
orVertical risers where
within both a 6-foot radius of another pole supporting unprotected
supply conductors. and within a vertical distance of 3 feet above or
6 feet below the level of any unprotected supply conductor shall be covered.
Final Version
Rule 84.6-E
84.6-E.
Risers
Risers of wires or underground
cables shall be covered from the ground line to a level not less than 8 feet
above the ground line by one of the following:
(1) Grounded (see definition 21.2) iron or steel pipe, metal U-guard or other metallic covering of equal strength or;
(2)
Conduit or U-shaped molding meeting the
requirements as specified in
Rule 22.2.
Risers shall be covered by a suitable protective covering as defined in Rule 22.2, for a vertical distance of 3 feet above to 6 feet below the level of unprotected supply conductors supported on the same pole or structure, or within a 6-foot radius of another pole supporting unprotected supply conductors.