Original Version
G.O. 128 Rule 21.5
21.5 Grounded means connected to earth by an intentional ground connection or by an unintentional conducting path.
A. Effectively
Grounded (Effective Ground) means permanently connected to earth through a
ground connection or connections of sufficiently low impedance and having
sufficient current-carrying capacity to prevent the building up of voltages
which may result in undue hazard to connected equipment or to persons.
If an
impedance of less than 25 ohms is not obtained, the equivalent of a ground
conductor not less than No.6 A WG copper connected to two corrosion resisting
rods, not less than i inch in diameter and 8 feet in length and continuous
throughout, driven to a minimum depth of 8 feet in the earth at not less than 6
foot centers, will be considered an effective ground for the purpose of these
rules.
Strikeout and Underline Version
G.O. 128 Rule 21.5
21.5
Grounded
means connected to earth by an intentional ground connection or by an
unintentional conducting a conductive path.
A. Effectively
Grounded (Effective Ground) means permanently connected to earth through a
ground connection or connections of sufficiently low impedance and having
sufficient current-carrying capacity to prevent the building up of voltages
which may result in undue hazard to persons or to connected equipmentor to persons
If an impedance of less than 25 ohms is not obtained, the equivalent of
a ground conductor not less than No.6 A WG copper connected to two corrosion
resisting rods, not less than i inch in diameter and 8 feet in length and
continuous throughout, driven to a minimum depth of 8 feet in the earth at not
less than 6 foot centers, will be considered an effective ground for the
purpose of these rules.
Final Version
G.O. 128 Rule 21.5
21.5 Grounded means connected to earth by a conductive path.
A. Effectively
Grounded (Effective Ground) means permanently connected to earth through a
ground connection or connections of sufficiently low impedance and having
sufficient current-carrying capacity to prevent the building up of voltages which
may result in undue hazard to persons or to connected equipment.
If an impedance of less than 25 ohms is not obtained, the equivalent of
a ground conductor not less than No.6 A WG copper connected to two corrosion
resisting rods, not less than i inch in diameter and 8 feet in length and
continuous throughout, driven to a minimum depth of 8 feet in the earth at not
less than 6 foot centers, will be considered an effective ground for the
purpose of these rules.