Original Version
Rule 83.4-A1
83.4-A1) Bonds between Separate Communication Messengers or Guys above or below Electric Circuits: Bonds are required between separate communication messengers or guys, attached above or below electric supply circuits, railway signal circuits or Class T electric railroad or trolley circuits on the same pole line system, at all dead–end poles and at intervals not to exceed 1,500 feet.
Strikeout and Underline Version
Rule 83.4-A1
83.4-A1)
Bonds between Separate Communication
Messengers or Guys above or below Electric Circuits: Bonds are required between separate communication
messengers or guys, attached above or below electric supply circuits, railway
signal circuits or Class T electric railroad or trolley circuits on the same
pole line system, at all dead–end poles and at intervals not to exceed 1,500
1,320 feet.
Final Version
Rule 83.4-A1
83.4-A1) Bonds between Separate Communication Messengers or Guys above or below Electric Circuits: Bonds are required between separate communication messengers or guys, attached above or below electric supply circuits, railway signal circuits or Class T electric railroad or trolley circuits on the same pole line system, at all dead–end poles and at intervals not to exceed 1,320 feet.