Rule 86.8-C

 

86.8-C.    Voltage Requirements

Insulators used in guys on communication lines shall be so designed that their dry flashover voltage is not more than 75% of their puncture voltage at the operating frequencies of supply lines to which guys are exposed.

Insulation used in guys on communication lines shall have a dry flashover voltage not less than as specified in Table 16 when tested in accordance with the Standards (No. 41, March, 1930) of the American Institute of Electrical Engineers under the maximum mechanical loadings specified by this Order for the guy construction involved.


Strikeout and Underline Version

Rule 86.8-C

 

86.8-C.    Voltage Requirements

Insulatorsused in guys on communication lines shall be so designed that their dry flashover voltage is not more than 75% of their puncture voltage at the operating frequencies of supply lines to which guys are exposed.

Insulators Insulation used in guys on communication lines shall have a dry flashover voltage not less than as specified in Table 16 when tested in accordance with the Standards (No. 41, March, 1930) of the American Institute of Electrical Engineers American National Standard (ANSI Standard C29. 1-198) under the maximum mechanical loadings specified by this Order for the guy construction involved.


Final Version

Rule 86.8-C

 

86.8-C.    Voltage Requirements

Insulators used in guys on communication lines shall be so designed that their dry flashover voltage is not more than 75% of their puncture voltage at the operating frequencies of supply lines to which guys are exposed.

Insulators used in guys on communication lines shall have a dry flashover voltage not less than as specified in Table 16 when tested in accordance with the American National Standard (ANSI Standard C29. 1-198) under the maximum mechanical loadings specified by this Order for the guy construction involved.