Rule 87.7-D
87.7-D. New Rule
Strikeout and Underline Version
Rule 87.7-D
87.7-D. Risers
(1)
Covered from Ground Level to
8 Feet above the Ground:
Risers shall be protected from
the ground level to a level not less than 8 feet above the ground by:
a)
Securely or effectively
grounded iron or steel pipe (or other covering at least of equal stre
ngth). When metallic sheathed cable rising from underground non–metallic
conduit is protected by metallic pipe or moulding, such pipe or moulding shall
be effectively grounded as specified in Rule
21.2–A
, or
b)
Non–metallic conduit
or rigid U–shaped moulding. Such conduit or
moulding shall be of material as specified in
Rule 22.2
.
(2)
Covered
from 8 Feet above the Ground Level and Above:
a)
Risers
shall be covered by a suitable protective covering, as defined in Rule 22.2
where within a vertical distance of 3 feet above or 6 feet below the level
of unprotected supply conductors when supported on the same pole or structure
or within a 6–foot radius of another pole supporting unprotected supply conductors,
except that when the riser is protected by a guard arm installed in accordance
with Rule 87.4–C3
the 6 feet may be reduced to not less than 4 feet.
Final Version
Rule 87.7-D
87.7-D. Risers
(1)
Covered from Ground Level to
8 Feet above the Ground:
Risers shall be protected from
the ground level to a level not less than 8 feet above the ground by:
a)
Securely or effectively
grounded iron or steel pipe (or other covering at least of equal stre
ngth). When metallic sheathed cable rising from underground non–metallic
conduit is protected by metallic pipe or moulding, such pipe or moulding shall
be effectively grounded as specified in Rule
21.2–A
, or
b)
Non–metallic conduit
or rigid U–shaped moulding. Such conduit or
moulding shall be of material as specified in
Rule 22.2
.
(2)
Covered
from 8 Feet above the Ground Level and Above:
a)
Risers
shall be covered by a suitable protective covering, as defined in Rule 22.2
where within a vertical distance of 3 feet above or 6 feet below the level
of unprotected supply conductors when supported on the same pole or structure
or within a 6–foot radius of another pole supporting unprotected supply conductors,
except that when the riser is protected by a guard arm installed in accordance
with Rule 87.4–C3
the 6 feet may be reduced to not less than 4 feet.