Original Version
Rule 84.4-E
84.4-E.
Above Or
Beside Buildings, Bridges And Other Similar Structures
Conductors (including cables) shall be so arranged as to
hamper and endanger firemen and workmen as little as possible in the
performance of their duties. The basic clearances of conductors from buildings
are specified in Table 1, Cases 6 and 7. The requirements of Table 1, Case 7,
also apply at fire escapes, exits, windows, etc., at which human contact may be
expected.
Communication cables are not required to be any specified
distance from the sides of buildings, but they shall be installed so that they
do not interfere with the free us of fire escapes, exits, etc.
The vertical clearance of communication conductor (including cables) above buildings as specified in Table 1, Case 6, may be
reduced to not less than 2 feet under the following conditions:
Over roofs of 3/8 pitch
(37 degrees from the horizontal) or greater,
Over roofs where the conductor does not overhang the
building by more than 6 feet.
See Rule 84.8-C4 for service drop clearance requirements
Strikeout and Underline Version
Rule 84.4-E
84.4-E.
Above Or
Beside Buildings, Bridges And Other Similar Structures
Conductors should be (including cables) shall so
arranged so as not to hamper or endanger and
firefighters and firemen workers workmenperformas little as possible in
the ing anceof their duties. The basic clearances
of communication conductors from buildings are specified in Table 1,
Cases 6 and 7, Column B. The requirements of Table 1, Case 7, Column
B also apply to at fire escapes, exits, windows, etc.,
and any other points of entrance or exit where human contact might be
expected. Communication cables are not required to be any specified
distance from the sides of buildings, bridges and other similar structures,
but they shall be installed so that they do not interfere with the free us of
fire escapes, exits, at which human contact may be expected. and any other points of entrance or exit
where human contact might be expected.etc.,
The vertical clearance of communication conductor (including cables) above buildings as specified in Table 1, Case 6, Column B
may be reduced to not less than 2 feet under the following conditions:
(1)
Over
roofs of 3/8 pitch (37 degrees
from the horizontal) or greater, or
(2)
Over
roofs where the conductor does not overhang the building by more than 6 feet.
See Rule 84.8-C4 for service drop clearance requirements
Final Version
Rule 84.4-E
84.4-E. Above Or Beside Buildings, Bridges And Other Similar Structures
Conductors should be arranged so as not to hamper or endanger firefighters and workers performing their duties. The basic clearances of communication conductors from buildings are specified in Table 1, Cases 6 and 7, Column B. The requirements of Table 1, Case 7, Column B also apply to fire escapes, windows, and any other points of entrance or exit where human contact might be expected.
Communication cables are not required to be any specified distance from the sides of buildings, bridges and other similar structures, but they shall be installed so that they do not interfere with the free us of fire escapes, exits, and any other points of entrance or exit where human contact might be expected.
The vertical clearance of communication conductor (including cables) above buildings as specified in Table 1, Case 6, Column B may be reduced to not less than 2 feet under the following conditions:
(1)
Over
roofs of 3/8 pitch (37 degrees
from the horizontal) or greater, or
(2) Over roofs where the conductor does not overhang the building by more than 6 feet.
See Rule 84.8-C4 for service drop clearance requirements