General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
56.2 Use
Where mechanical loads imposed on poles, towers, or structures
are greater than can be supported with safety factors as specified in
Rule 44
, additional strength shall be provided by the use of guys or other suitable
construction.
Where guys are used with poles or similar structures capable
of considerable deflection before failure, the guys shall be able to support
the entire load, the pole below the point of guy attachment acting merely
as a strut.
Guys shall be attached to structures, as nearly as practicable,
at the center of load. They shall be maintained taut and of such strength
as to meet the safety factors of Rule 44
.