General Order 95
  
Section VII
  
Detailed Construction Requirements for Trolley and Electric Railway
  Contact and Feeder Conductors and Their Supporting Messengers,
  Span Wires, Etc. (Class T Circuits)
  
77.6    Requirements for Sectionalizing Insulators
     
Span wires, backbones, messengers, etc., shall be sectionalized 
 by means of insulators placed in them in accordance with the following rules.
     
    
    
Insulators used in the sectionalizing of span wires, backbones 
 and messengers shall conform to the specifications for guy insulators as 
given in Rule 56.8
    based on the voltage of the trolley contact conductor.
       
    
    
A.    Span Wires
                 
    
(1)     Supporting One Contact Conductor: One insulator  (preferably of
the interlocking strain type) shall be placed in the span wire between 4
feet and 5 feet (measured along the span wire) from each hanger  or point
of support of the trolley contact conductor and its appurtenances  which
have electrical contact therewith. Where the angle between the span  wire
and contact conductor is so small that the insulator will interfere with
the movement of the current collecting device, such insulator may be installed
more than 5 feet (measured along the span wire) from the contact conductor,
but shall be not more than 4 feet in a perpendicular direction from the contact
conductor (see Appendix G, Figs. 
        68
 and 69
).
             
        
A second insulator (preferably of the interlocking 
 strain type) shall be placed in the span wire not less than 6 feet and not 
 more than 9 feet from the pole or structure.
                 
        
The separation between the first and second insulators 
 shall be at least 4 feet wherever practicable but where the distance between 
 the pole or structure and the trolley contact conductor is less than 14 feet
 the second insulator shall be not less than 15 inches from the surface of
 the pole or structure and outside of the climbing and work spaces.
                     
        
Where the span wire is attached to a building, 
 the second insulator shall be not less than 3 feet from the building.
                         
        
Where the support is a wood pole and all
facilities supported thereon are of one ownership and are operated and maintained
by the same crews of workmen, the second insulator may be omitted.
                             
        
(2) 
           Supporting Two or More Contact  Conductors of Same Polarity: Span 
wires supporting two or more contact  conductors of the same polarity shall 
be sectionalized in accordance with  Rule 77.6–A1
, above. If the contact conductors are more than 18 feet apart,  an insulator
shall be placed in the section of the span wire between the contact conductors
at a point between 4 feet and 5 feet from each contact conductor hanger or
support. Where the distance between contact conductors is less than 18 feet
this provision does not apply.
                                 
        
(3) 
           Supporting Contact Conductors  of Opposite Polarity: Span wires
supporting contact conductors of opposite  polarity shall be sectionalized
in accordance with the provisions of Rule 77.6–A1
. For this purpose each pair of positive and negative contact conductors
 shall be treated as a single conductor, the measurement being made to the
 nearest contact conductor of the pair.
                                     
        
A span wire which supports 
 trolley contact conductors of opposite polarity shall have an insulator placed
 in between the hangers of such opposite polarity conductors unless the hangers
 have a dry flashover insulating value of 6,000 volts or more.
                                         
        
Where contact conductors 
 are more than 18 feet apart an insulator shall be placed in the section of
 the span wire between such contact conductors at a point between 4 feet and
 5 feet from each contact conductor hanger or support.
                                             
        
(4) 
           Feeder Cables  Used as Span Wires: One insulator (preferably of
the interlocking strain  type) shall be placed in such a span wire at a distance 
of not less than 15 inches from the surface of the pole supporting the feeder 
(except where only Class T circuits of the same polarity are installed on 
the pole as specified  in Rule 74.4–D
) and outside of the climbing and working spaces on such pole.
                                                 
        
A second insulator 
 (preferably of the interlocking strain type)shall be placed at the point 
where the feeder cable terminates, which point shall be not less than 1 foot 
nor more than 5 feet beyond the last trolley contact conductor to which it 
is electrically connected.
                                                     
        
A third insulator 
 (preferably of the interlocking strain type)shall be placed in the remaining 
 section of the span wire at a distance of not less than 6 feet and not more 
 than 9 feet (measured along the span wire) from the opposite pole or structure 
 (see Appendix G,
Figure 71
).
                                                         
        
In catenary 
 construction, the point at which the second insulator is placed shall be 
not less than 1 foot plus the distance between the messenger and contact conductor,
nor more than 5 feet, beyond the last trolley contact conductor to which
the feeder cable is electrically connected.
                                                             
        
(5)    Feeder Cables Used as Auxiliary Span Wires: Where the feeder cable 
 is used as an auxiliary span wire, it shall be installed and maintained at
 a distance of not less than 18 inches above the span wire, or it may be
attached  to the span wire as provided in 
        Rule 74.4–G3
. Auxiliary feeder cable spans  shall be sectionalized in accordance with
the provisions of Rule 77.6–A4
 above (see Appendix
G, Figure 67
). In this type of construction the attachment of the feeder to the trolley
contact conductor shall preferably be made on the side of the contact conductor
opposite approaching traffic (see 
        Appendix G, Figure 70)
.
                                                                 
        
(6) 
           Feeder Cables Crossing Poles: Where a feeder cable crosses the 
pole  laterally, it shall not impair the climbing or working spaces and it 
is recommended  that the cable be installed under a crossarm in fiber conduit 
or other suitable  protective covering (see 
        Rule 54.6–C
).
                                                                     
B. Backbones and Pull–offs
(1) 
           Backbones Supported on Crossarms: A backbone which is supported
 by insulators on crossarms, pole brackets or trolley brackets shall be treated 
 as a Class T line conductor except in that section between the last such 
support and its dead–end attachment where it shall be sectionalized by means 
of an insulator placed not less than 6 feet and not more than 9 feet from 
each support (see 
        Appendix G, Figure 72
).
                                                                        
                                                                        
                                                                        
                                                                        
        
(2) 
           Backbone Attached to Poles: A backbone run between and attached
 directly to poles shall have insulators placed in it not less than 6 feet
 and not more than 9 feet (measured along the line of the backbone) from
the  points of attachment to the poles (see 
        Appendix G, Figure 73
).
                                                                        
      
        
(3) 
           Pull–offs: Each pull–off from the contact conductor to that section 
 of the backbone between the insulators specified in Rule 77.6–B2,
 above, shall have an insulator placed in it at a distance between 4 and
5 feet from the nearest contact conductor; or if this is not practicable,
the insulator shall be installed as far as possible from the contact conductor.
Any pull–off from the contact conductor to a point between the supporting
pole and the backbone insulator shall have two insulators installed in it
and the insulator nearest the pole or the backbone shall be not less than
15 inches from the center line of pole and shall be outside the climbing
and working spaces (see Appendix G, Figure 73).
                                                                        
          
C.    Brackets or Bracket Arms
                                                                        
          
                                                                        
                                                                                                
   
        
In bracket construction span wires which support, or are attached to other 
 span wires which support, trolley contact conductors or appurtenances in 
electrical contact therewith shall be sectionalized as follows:
                                                                        
                
                
(1)    General: An insulator shall be inserted in the span wire between 
 the suspension of the trolley contact conductor and each point of support 
 of the span wire, such insulators to be not less than 12 inches from the 
nearest trolley contact conductor (see Appendix G, Figs. 
74
 and 75
).
                                                                        
                       
        
Where the span wire supports contact conductors of opposite polarity an
 additional insulator shall be inserted between the hangers of such opposite
 polarity conductors unless the hangers have a dry flashover insulating value
 of 6,000 volts or more.
                                                                        
                        
        
(2)     EXCEPTIONS: Where the brackets are supported on wood poles which 
 support only conductors of one ownership, the insulators between the hangers 
 and points of span wire support may be omitted (see Appendix G, Figs. 
        76
 and 77
).
                                                                        
                               
        
Where brackets and their lift spans are suitably insulated along their 
length  (perpendicular to the poles) and from the span wire, that part of 
                                                                                                      
        Rule 77.6–C1
  which prescribes an insulator between the contact conductor suspension
and  the point of bracket support need not apply (see 
        Appendix G, Figure 78
)
                                                                        
                                   
        
Insulators placed in metal brackets and lift spans shall be not less than 
 12 inches radially from the trolley contact conductor (see 
        Appendix G, Figure  79
).
                                                                        
                                    
        
(3) 
           Feeder Conductors: Feeder wires used as bracket span wires shall 
 be sectionalized as follows:
                                                                        
                                           
        
One insulator (preferably of the interlocking strain type) shall be placed 
 in the span wire at a distance of not less than 15 inches from the surface 
 of poles (except where only Class T circuits of the same polarity are installed 
 on the pole as specified in Rule 74.4–D
) and outside the climbing and working  spaces. A second insulator shall
be placed at the point where the feeder terminates (see
 Appendix G, Figure 80
).
                                                                        
                                               
        
On high speed lines it is recommended that in lieu of this type of construction 
 the bracket span be installed as specified in Rule 77.6–C1
 and the feeder  span be installed as a bracket guy or lift span. In this
case, one insulator  shall be placed in the lift span so that the horizontal
distance between the insulator and the surface of the supporting pole or
structure shall be not less than 15 inches, and a second insulator shall
be placed along the line of this lift span adjacent to the point of attachment
to the bracket.
                                                                        
                                                
D.    Messengers
                                                                        
                                                
                                                                        
                                                                                                                                                                            
   
        
When an extended messenger is treated as a guy, the requirements specified 
 for guys shall be met.