General Order 95
Section III
Requirements for All Lines
Table 2–A Minimum Clearances of Wires from Signs Mounted on Buildings
and Isolated Structures (a)
(Letter References Denote Modifications of Minimum Clearances as Referred
to in Notes Following this Table)
Case |
Nature of ClearanceType of Sign |
A |
B |
C |
D |
E |
1 |
Vertical clearance above all signs upon
which men can walk |
8 Feet |
8 Feet |
8 Feet |
12 Feet |
20 Feet (g)
|
2 |
Vertical clearance above all signs upon
which men cannot walk |
2 Feet |
2 Feet |
3 Feet |
8 Feet |
20 Feet (g)
|
3 |
Vertical clearance under signs which are
illuminated |
2 Feet (c)
|
2 Feet (e)
|
3 Feet |
Prohibited (f)
|
Prohibited |
4 |
Vertical clearance under signs which are
non–illuminated |
6'' (d)
|
1 Foot |
3 Feet |
Prohibited (f)
|
Prohibited |
5 |
Horizontal clearance from signs which are
illuminated |
3 Feet (c)
|
3 Feet (e)
|
3 Feet |
6 Feet |
15 Feet (h)
|
6 |
Horizontal clearance from signs which are
non–illuminated |
6'' (d)
|
1 Foot |
3 Feet |
6 Feet |
15 Feet (h)
|
References to Rules Modifying Minimum Clearances in Table 2–A
(a) These clearances do not apply to service drop conductors
which are attached to signs for the purpose of serving such signs.
(b) Nothing herein contained shall be construed as authorization
of noncompliance with standards of the california division of industrial
safety, including article e760–2 entitled “provision for preventing accidents
due to proximity of high-voltage lines, 24 Cal. Adm. Code, Part 3, Basic
Electrical Regulations.
(c) May be reduced to 6 inches provided illuminated sign
is grounded.
(d) May be reduced if adequate separation is provided
by means of a suitable non–conducting separator.
(e) May be reduced to 1 foot for communication open wire
conductors only, provided illuminated sign is grounded
(f) When conductors are at a level of 8 feet or more
below the level of the lowest portion of the sign but not vertically under
the sign, no horizontal clearance is required between the vertical planes
through the conductor nearest the sign and the vertical projection of the
extremities of the sign. Also note (b)
above.
(g) Shall be increased by 0.04 foot per kV in excess
of 300 kV.
(h) Not applicable to certain kinds of conductors.
Note: Resolution E–1068 dated May 31, 1960 authorized
the addition of the above Rule 39 and Table 2–A to be effective July 1,
1960. Revised March 30, 1968 by Decision No. 73813.