Previous Rule Change Main Page Resolution Decision Main Page Change List for this Rule Search Decision Number 14-02-015 Decision Number 14-02-015 Next Rule Change

Original Version
Appendix F - Part 1 - #8

8. Crossarms–Horizontal Loads
Power Circuits

The point of maximum bending moment will be at the crossarm through bolt attaching the arm to the pole, at which point the cross section of the arm is reduced by the amount of the bolt hole. Crossarms supporting the 60 kV wires are to be Douglas fir, dense, dimensions 4–3/4” x 5–3/4” x 12’, bored as illustrated below.

8

The section through the arm and the method of computing the fiber stress is shown below.0

Long–time loading: Since longitudinal conductor loads are normally balanced, long–time horizontal loading of the power circuit crossarms need not be considered.

Single arm, Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches
9

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

10

Fiber Stress = Bending moment divided by

11

As the allowable value for modulus of rupture in bending under maximum loading conditions is 6,300 lbs per sq. in. (see Table 5 , Rule 48.1 ), a single crossarm of the size chosen provides a safety factor of only 0.70 for the assumed load at maximum loading conditions, whereas the provisions of Rule 47.5 require a safety factor of unity. Double arms will, therefore, be used in this problem to meet the strength requirements applicable to crossarms at end supports of crossings. Double crossarm construction of this type with separation maintained by space bolts is assumed to have a horizontal strength equivalent to 130% of the sum of the strengths of two single crossarms acting independently.

Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches

Single arm section modulus (same as previously calculated) = 19.0 inches

Double arm section modulus = 19.0 x 2 x 1.3 = 49.4 inches

12
As the allowable modulus of rupture for short–time loading is 6,300 lbs per sq. in. then the double crossarms under these conditions will provide a safety factor of 1.91, which meets the unity safety factor required by Rule 47.5.
Private Communication Circuit

At the crossing span, double crossarms are used on account of dead–end construction due to change of conductor size. Current practice provides for this method of construction although a singlearm has sufficient strength as is found form the following calculations of modulus of rupture under the two limiting conditions of loading:

13

Long–time loading, 60°F and no wind

Bending moment = 448 x 18 = 8,064 pound–inches

14

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

15

The allowable value for modulus of rupture in bending is 0.55 x 6,300 = 4,465 pounds per square inch and therefore with a single arm the factor of safety under conditions of long–time loading is 2.69.

Maximum Loading

Bending moment = 570 x 18 = 10,260 pound–inches

Section modulus = 6.26 inches3 (as per calculations above)

16
The allowable value for modulus of rupture in bending, under maximum loading conditions, is 6,300 pounds per sq. in., therefore a single arm provides a safety factor of 3.84 under these maximum loading conditions.

 

Strikeout and Underline Version
Appendix F - Part 1 - #8

8. Crossarms–Horizontal Loads
Power Circuits

The point of maximum bending moment will be at the crossarm through bolt attaching the arm to the pole, at which point the cross section of the arm is reduced by the amount of the bolt hole. Crossarms supporting the 60 kV wires are to be Douglas fir, dense, dimensions 4–3/4” x 5–3/4” x 12’, bored as illustrated below.

8

The section through the arm and the method of computing the fiber stress is shown below.0

Long–time loading: Since longitudinal conductor loads are normally balanced, long–time horizontal loading of the power circuit crossarms need not be considered.

Single arm, Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches
9

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

10

Fiber Stress = Bending moment divided by

11

As the allowable value for modulus of rupture in bending under maximum loading conditions is 6,300 lbs per sq. in. (see Table 5 , Rule 48.1 ), a single crossarm of the size chosen provides a safety factor of only 0.70 for the assumed load at maximum loading conditions, whereas the provisions of Rule 47.547.3 require a safety factor of unity. Double arms will, therefore, be used in this problem to meet the strength requirementsapplicable to crossarms at end supports of crossings. Double crossarm construction of this type with separation maintained by space bolts is assumed to have a horizontal strength equivalent to 130% of the sum of the strengths of two single crossarms acting independently.

Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches

Single arm section modulus (same as previously calculated) = 19.0 inches

Double arm section modulus = 19.0 x 2 x 1.3 = 49.4 inches

12

As the allowable modulus of rupture for short–time loading is 6,300 lbs per sq. in. then the double crossarms under these conditions will provide a safety factor of 1.91, which meets the unity safety factor required by Rule 47.547.3.

Private Communication Circuit

At the crossing span, double crossarms are used on account of dead–end construction due to change of conductor size. Current practice provides for this method of construction although a singlearm has sufficient strength as is found form the following calculations of modulus of rupture under the two limiting conditions of loading:

13

Long–time loading, 60°F and no wind

Bending moment = 448 x 18 = 8,064 pound–inches

14

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

15

The allowable value for modulus of rupture in bending is 0.55 x 6,300 = 4,465 pounds per square inch and therefore with a single arm the factor of safety under conditions of long–time loading is 2.69.

Maximum Loading

Bending moment = 570 x 18 = 10,260 pound–inches

Section modulus = 6.26 inches3 (as per calculations above)

16
The allowable value for modulus of rupture in bending, under maximum loading conditions, is 6,300 pounds per sq. in., therefore a single arm provides a safety factor of 3.84 under these maximum loading conditions.

Final Version
Appendix F - Part 1 - #8

8. Crossarms–Horizontal Loads
Power Circuits

The point of maximum bending moment will be at the crossarm through bolt attaching the arm to the pole, at which point the cross section of the arm is reduced by the amount of the bolt hole. Crossarms supporting the 60 kV wires are to be Douglas fir, dense, dimensions 4–3/4” x 5–3/4” x 12’, bored as illustrated below.

8

The section through the arm and the method of computing the fiber stress is shown below.0

Long–time loading: Since longitudinal conductor loads are normally balanced, long–time horizontal loading of the power circuit crossarms need not be considered.

Single arm, Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches
9

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

10

Fiber Stress = Bending moment divided by

11

As the allowable value for modulus of rupture in bending under maximum loading conditions is 6,300 lbs per sq. in. (see Table 5, Rule 48.1), a single crossarm of the size chosen provides a safety factor of only 0.70 for the assumed load at maximum loading conditions, whereas the provisions of Rule 47.3 require a safety factor of unity. Double arms will, therefore, be used in this problem to meet the strength requirements applicable to crossarms at end supports of crossings. Double crossarm construction of this type with separation maintained by space bolts is assumed to have a horizontal strength equivalent to 130% of the sum of the strengths of two single crossarms acting independently.

Maximum loading, 25°F and an 8 lb wind

Bending moment = 2,605 x 66 = 171,930 pound–inches

Single arm section modulus (same as previously calculated) = 19.0 inches

Double arm section modulus = 19.0 x 2 x 1.3 = 49.4 inches

12

As the allowable modulus of rupture for short–time loading is 6,300 lbs per sq. in. then the double crossarms under these conditions will provide a safety factor of 1.91, which meets the unity safety factor required by Rule 47.3.

Private Communication Circuit

At the crossing span, double crossarms are used on account of dead–end construction due to change of conductor size. Current practice provides for this method of construction although a singlearm has sufficient strength as is found form the following calculations of modulus of rupture under the two limiting conditions of loading:

13

Long–time loading, 60°F and no wind

Bending moment = 448 x 18 = 8,064 pound–inches

14

b = 5.75” – 0.69 = 5.06”

d = 4.75”

s = 11/16” = 0.69”

15

The allowable value for modulus of rupture in bending is 0.55 x 6,300 = 4,465 pounds per square inch and therefore with a single arm the factor of safety under conditions of long–time loading is 2.69.

Maximum Loading

Bending moment = 570 x 18 = 10,260 pound–inches

Section modulus = 6.26 inches3 (as per calculations above)

16
The allowable value for modulus of rupture in bending, under maximum loading conditions, is 6,300 pounds per sq. in., therefore a single arm provides a safety factor of 3.84 under these maximum loading conditions.