Rule 59.2
59.2 Applicability
The following rules cover certain special details for common
neutral systems where the neutral conductor is common to primary circuits
of less than 21,000 volts and secondary circuits of 0-750 volts supplied therefrom.
These rules are supplemental to the rules given for supply lines in general
and to other detailed construction requirements for supply lines.
Strikeout and Underline Version
Rule 59.2
59.2 Applicability
The following rules cover certain special details for common
neutral systems where the neutral conductor is common to primary circuits
of less than 21,000 22,500 volts and secondary circuits
of 0-750 volts supplied therefrom. These rules are supplemental to
the rules given for supply lines in general and to other detailed construction
requirements for supply lines.
Final Version
Rule 59.2
59.2 Applicability
The following rules cover certain special details for common
neutral systems where the neutral conductor is common to primary circuits
of less than 22,500 volts and secondary circuits of 0-750 volts supplied
therefrom. These rules are supplemental to the rules given for supply
lines in general and to other detailed construction requirements for supply
lines.