Rule 44.1

 

44.1    Installation and Reconstruction,

 

Lines and elements of lines, upon installation or reconstruction, shall provide as a minimum the safety factors specified in Table 4 for vertical loads and loads transverse to lines and for loads longitudinal to lines except where longitudinal loads are balanced or where there are changes in grade construction (see Rules 47.3, 47.4 and 47.5)

 

Table 4

Minimum Safety Factors

Element of Line

Grade of Construction

Grade “A”

Grade “B”

Grade “C”

Grade “F”

Conductors, splices and conductor fastenings (other than tie wires)

2

2

2

1

Pins

2

2

1

1

Pole line hardware

 2

 2

2

2

Line insulators (mechanical)

3

2

2

2

Guy Insulators (mechanical)

Interlocking

 2

2

2

2

Noninterlocking wood

 3

3

3

--

Noninterlocking glass fiber

3

2(a)

2(b)

--

Guys, except in light loading districts

2

2

2

1 ½

Guys, in light loading rural districts

2

1 ½

1 ½

1 ½

Messengers and span wires

2

2

2

2

Wood poles

4

3

2

1

Metallic Service and Meter Poles

-

2

2

--

Structural or tubular metallic poles, towers, crossarms and steel members of foundations

1 ½ (c)

1 ¼ (c)

1 ¼(c)

--

Foundations against uplift

1 ½

1 ½

1 ½

--

Foundations against depression

3

2

2

--

Reinforced concrete poles

4

3

3

--

Crossarms (wood)

2

2

2

1

 

(a)    Insulators are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement or other conditions subsequent to installation) to less than 95 percent of the safety factor specified in Rule 44.1.

 

(b)    Insulator are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement, or other conditions subsequent to installation) to less than 75 percent of the safety factor specified in Rule 44.1.

 

(c)    For aluminum members subject to tension caused by one or more estimated loads and where the critical load combination for the tension member would not endanger adjacent compression members, the factor of safety on ultimate tension shall be 2 for Grade “A” construction and 1.67 for Grades “B” and “C” construction


Strikeout and Underline Version

Rule 44.1

 

44.1    Installation and Reconstruction

 

Lines and elements of lines, upon installation or reconstruction, shall provide as a minimum the safety factors specified in Table 4 for vertical loads and loads transverse to lines and for loads longitudinal to lines except where longitudinal loads are balanced or where there are changes in grade construction (see Rules 47.3, 47.4 and 47.5)

 

Table 4

Minimum Safety Factors

Element of Line

Grade of Construction

Grade “A”

Grade “B”

Grade “C”

Grade “F”

Conductors, splices and conductor fastenings (other than tie wires)

2

2

2

1

Pins

2

2

1

1

Pole line hardware

 2

 2

2

2

Line insulators (mechanical)

3

2

2

2

Guy Insulators (mechanical)

Interlocking

 2

2

2

2

Noninterlocking wood

 3

3

3

--

Noninterlocking glass fiber

3

2(a)

2(b)

--

Guys, except in light loading districts

2

2

2

1 ½

Guys, in light loading rural districts

2

1 ½

1 ½

1 ½

Messengers and span wires

2

2

2

2

Wood poles

4

3

2

1

Metallic Service and Meter Poles

-

2

2

--

Structural or tubular metallic poles, towers, crossarms and steel members of foundations

1 ½ (c)

1 ¼ (c)

1 ¼(c)

--

Foundations against uplift

1 ½

1 ½

1 ½

--

Foundations against depression

3

2

2

--

Reinforced concrete poles

4

3

3

--

Crossarms (wood)

2

2

2

1

Prestressed Concrete Poles, Structures, and Crossarms

1.8

1.5

1.5

--

 

(a)    Insulators are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement or other conditions subsequent to installation) to less than 95 percent of the safety factor specified in Rule 44.1.

 

(b)    Insulator are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement, or other conditions subsequent to installation) to less than 75 percent of the safety factor specified in Rule 44.1.

 

(c)    For aluminum members subject to tension caused by one or more estimated loads and where the critical load combination for the tension member would not endanger adjacent compression members, the factor of safety on ultimate tension shall be 2 for Grade “A” construction and 1.67 for Grades “B” and “C” construction


Final Version

Rule 44.1

 

44.1    Installation and Reconstruction,

 

Lines and elements of lines, upon installation or reconstruction, shall provide as a minimum the safety factors specified in Table 4 for vertical loads and loads transverse to lines and for loads longitudinal to lines except where longitudinal loads are balanced or where there are changes in grade construction (see Rules 47.3, 47.4 and 47.5)

 

Table 4

Minimum Safety Factors

Element of Line

Grade of Construction

Grade “A”

Grade “B”

Grade “C”

Grade “F”

Conductors, splices and conductor fastenings (other than tie wires)

2

2

2

1

Pins

2

2

1

1

Pole line hardware

 2

 2

2

2

Line insulators (mechanical)

3

2

2

2

Guy Insulators (mechanical)

Interlocking

 2

2

2

2

Noninterlocking wood

 3

3

3

--

Noninterlocking glass fiber

3

2(a)

2(b)

--

Guys, except in light loading districts

2

2

2

1 ½

Guys, in light loading rural districts

2

1 ½

1 ½

1 ½

Messengers and span wires

2

2

2

2

Wood poles

4

3

2

1

Metallic Service and Meter Poles

-

2

2

--

Structural or tubular metallic poles, towers, crossarms and steel members of foundations

1 ½ (c)

1 ¼ (c)

1 ¼(c)

--

Foundations against uplift

1 ½

1 ½

1 ½

--

Foundations against depression

3

2

2

--

Reinforced concrete poles

4

3

3

--

Crossarms (wood)

2

2

2

1

Prestressed Concrete Poles, Structures, and Crossarms

1.8

1.5

1.5

--

 

(a)    Insulators are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement or other conditions subsequent to installation) to less than 95 percent of the safety factor specified in Rule 44.1.

 

(b)    Insulator are to be replaced before safety factors have been reduced (due to deterioration or changes in construction, arrangement, or other conditions subsequent to installation) to less than 75 percent of the safety factor specified in Rule 44.1.

 

(c)    For aluminum members subject to tension caused by one or more estimated loads and where the critical load combination for the tension member would not endanger adjacent compression members, the factor of safety on ultimate tension shall be 2 for Grade “A” construction and 1.67 for Grades “B” and “C” construction