Rule 56.4-A3


56.4-A3)    New Rule


Strikeout and underline Version
Rule 56.4-A3


56.4-A
3)    Above Swimming Pools:

 

a)    Ungrounded portions of guys shall have radial clearances from the top edge of the swimming pool wall and vertical clearances above the highest water level of the pool of not less than 18 feet.

No ungrounded portion of guys may be installed less than 18 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.

No ungrounded portion of guys may be installed less than 12 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being the area within 6 feet radially of the diving board or platform and not over the water surface of the pool.

 

b)    Grounded portions of guys shall have vertical clearances above the highest water level of the pool of not less than 16 feet.

No grounded portion of guys may be installed less than 16 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.

No grounded portion of guys may be installed less than 8 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being the area within 3 feet radially of the diving board or platform and not over the water surface of the pool.


Final Version
Rule 56.4-A3


56.4-A3)    Above Swimming Pools:

 

a)    Ungrounded portions of guys shall have radial clearances from the top edge of the swimming pool wall and vertical clearances above the highest water level of the pool of not less than 18 feet.

No ungrounded portion of guys may be installed less than 18 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.

No ungrounded portion of guys may be installed less than 12 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being the area within 6 feet radially of the diving board or platform and not over the water surface of the pool.

 

b)    Grounded portions of guys shall have vertical clearances above the highest water level of the pool of not less than 16 feet.

No grounded portion of guys may be installed less than 16 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.

No grounded portion of guys may be installed less than 8 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being the area within 3 feet radially of the diving board or platform and not over the water surface of the pool.