Original Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
a) 0-7500 Volts in Triangular Configuration: A single conductor of a circuit of 0-7500 volts may be attached at the top of the pole provided the other conductors of the same circuit are on a crossarm and are not less than 2 feet vertically below the level of such single conductor, except that such a 2-foot vertical separation is not required for dead-ended conductors conforming to provisions of Rule 54.4-D7a.
Where this triangular configuration is used, all conductors of other circuits on crossarms on the pole shall be not less than 4 feet below the level of the lower conductors of the pole-top circuit and conductors of 0-750 volts in rack construction shall conform to the requirements of Rule 54.9-E.
b)    More than 7500 Volts: A single conductor of a circuit of more than 7500 
volts may be attached directly to the top of a pole or to a crossarm at the top 
of a pole at a distance less than as specified in Table 1, case 8, provided 
no apparatus carried on the pole is connected to the circuit so arranged except 
lighting arresters, a pole-top switch, or a transformer.  Where a transformer is 
connected to a circuit so arranged, a vertical clearance of not less than 30 
inches shall be maintained between the primary conductor directly above and the 
Unenergized metal parts of the transformer, as specified in Rule 
58.3-B3e.
Where this construction is used, all conductors of other 
circuits on the pole shall be not less than 6 feet below the pole-top conductor 
except that in rural districts the conductors of a 0-750 volt secondary circuit 
may be not less than 4 feet below the conductor level of such a primary circuit 
by means of which the secondary is supplied.
Dead ending of a conductor 
at top of pole under these provisions is optional with dead ending under the 
requirements of Rule 
54.4-D7b.
Strikeout and Underline Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
a) 
   0-7500 Volts in Triangular
Configuration:  A single conductor 
of a circuit of 0-7,500 volts may be attached at the top of a pole provided 
the other conductors of the same circuit are on a crossarm and are not less 
than 2 feet vertically below the level of such single conductor, except that 
such a 2-foot vertical separation is not required for dead-ended conductors.
Where 
this triangular configuration is used, all conductors of other circuits on crossarms 
on the pole shall be not less than 4 feet below the level of the lower conductors 
of the pole-top circuit and conductors of 0-750 volts in rack construction shall 
conform to the requirements of Rule 54.9-E.
b)    More than 7500 Volts: A single conductor of a circuit of 
more than 7,500 volts may be attached directly to the top of a pole or to a 
crossarm at the top of a pole at a distance less than as specified in Table 
1, Case 8, provided no apparatus carried on the pole is connected to the circuit 
so arranged except lightning arresters, a pole-top switch, or a transformer. 
Where a transformer is connected to a circuit so arranged, a vertical clearance 
of not less than 30 inches shall be maintained between the primary conductor 
directly above and the un-energized metal parts of the transformer, as specified 
in Rule, 58.3-B3e.
Where 
this construction is used, all conductors of other circuits on the pole shall 
be not less than 6 feet below the pole-top conductor except that in rural districts 
the conductors of a 0- 750 volt secondary circuit may be not less than 4 feet 
below the conductor level of such a primary circuit by means of which the secondary 
is applied supplied.
The 
dead ending of a conductor at top of pole under these provisions is optional 
with dead ending under the 
requirements of Rule 
54.4-D7b.
Final Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
a) 0-7500 Volts in Triangular Configuration: A single conductor of a circuit of 0-7,500 volts may be attached at the top of a pole provided the other conductors of the sa.me circuit are on a crossarm and are not less than 2 feet vertically below the level of such single conductor, except that such a 2-foot vertical separation is not required for dead-ended conductors.
Where this triangular configuration is used, all conductors of other circuits on crossarms on the pole shall be not less than 4 feet below the level of the lower conductors of the pole-top circuit and conductors of 0-750 volts in rack construction shall conform to the requirements of Rule 54.9-E.
b) More than 7500 Volts: A single conductor of a circuit of more than 7,500 volts may be attached directly to the top of a pole or to a crossarm at the top of a pole at a distance less than as specified in Table 1, Case 8, provided no apparatus carried on the pole is connected to the circuit so arranged except lightning arresters, a pole-top switch, or a transformer. Where a transformer is connected to a circuit so arranged, a vertical clearance of not less than 30 inches shall be maintained between the primary conductor directly above and the un-energized metal parts of the transformer, as specified in Rule, 58.3-B3e.
Where this construction is used, all conductors of other circuits on the pole shall be not less than 6 feet below the pole-top conductor except that in rural districts the conductors of a 0- 750 volt secondary circuit may be not less than 4 feet below the conductor level of such a primary circuit by means of which the secondary is supplied.
The dead ending of a conductor at top of pole under these provisions is optional.