Rule 54.8-A

 

54.8-A.    Material and Size

 

Supply service drops of 0-750 volts shall be of material and size as specified in Table 8 and Rule 49.4-C7a and shall have a weather-resistant covering at least equivalent to double-braid weatherproofing.

Note    Resolution No. 756 effective May 29, 1951 authorized the use of multiple conductor service drop cable with a bare neutral conductor for service drops of 0-750 volts provided that the attachment of such cable at the pole and building ends shall be by means of an insulator.

 

Strikeout and Underline Version

Rule 54.8-A

 

54.8-A.    Material and Size

 

Supply service drops of 0-750 volts shall be of material and size as specified in Table 8 and Rule 49.4-C7a and shall have a weather-resistant covering at least equivalent to double-braid weatherproofing.

 

Note    Resolution No. 756 effective May 29, 1951 authorized the use of multiple conductor service drop cable with a bare neutral conductor for service drops of 0-750 volts provided that the attachment of such cable at the pole and building ends shall be by means of an insulator.

 

Final Version

Rule 54.8-A

 

54.8-A.    Material and Size

 

Supply service drops of 0-750 volts shall be of material and size as specified in Table 8 and Rule 49.4-C7a.

 

Note    Resolution No. 756 effective May 29, 1951 authorized the use of multiple conductor service drop cable with a bare neutral conductor for service drops of 0-750 volts provided that the attachment of such cable at the pole and building ends shall be by means of an insulator.