Rule 56.4-F

 

56.4-F.    From Transformer Cases

 

All portions of guys 6 inches or more from the surface of poles or crossarms, at the guy attachment, shall be not less than 4 inches from transformer cases and hangers. Portions of guys within 6 inches of the surface of poles or crossarms to which they are attached shall be not less than 1 ½ inches from transformer cases and hangers.

 

Strikeout and Underline Version

Rule 56.4-F

 

56.4-F.    From Transformer Cases

 

All portions of guys 6 inches or more from the surface of poles or crossarms, at the guy’s point of attachment, shall be not be less than 4 inches from transformer cases and hangers. Portions of guys within 6 inches of the surface of poles or crossarms to which they are attached shall be not be less than 1 ½ inches from transformer cases and hangers.


Final Version

Rule 56.4-F

 

56.4-F.    From Transformer Cases

 

All portions of guys 6 inches or more from the surface of poles or crossarms, at the guy’s point of attachment, shall not be less than 4 inches from transformer cases and hangers. Portions of guys within 6 inches of the surface of poles or crossarms to which they are attached shall not be less than 1 ½ inches from transformer cases and hangers.