Original Version
Rule 56.4-F
56.4-F. From Transformer Cases
All portions of guys 6 inches or more from the surface of poles or crossarms, at the guy attachment, shall be not less than 4 inches from transformer cases and hangers. Portions of guys within 6 inches of the surface of poles or crossarms to which they are attached shall be not less than 1 ½ inches from transformer cases and hangers.
Strikeout and Underline Version
Rule 56.4-F
56.4-F. From Transformer Cases
All
portions of guys 6 inches or more from the surface of poles or crossarms, at the
guy’s point of attachment, shall be not be less than 4
inches from transformer cases and hangers. Portions of guys within 6 inches of
the surface of poles or crossarms to which they are attached shall be
not be less than 1 ½ inches from transformer cases and hangers.
Final Version
Rule 56.4-F
56.4-F. From Transformer Cases
All portions of guys 6 inches or more from the surface of poles or crossarms, at the guy’s point of attachment, shall not be less than 4 inches from transformer cases and hangers. Portions of guys within 6 inches of the surface of poles or crossarms to which they are attached shall not be less than 1 ½ inches from transformer cases and hangers.