Original Version
Table 3
| Table 3 Grades of Construction | ||
| Class of Circuits involved at upper level | Other facilities at lower level at crossing, conflicts or on poles jointly used | Grade of construction to be used at upper level | 
| E or H | Major Class C Circuits | “A” | 
| E, H or L | Major railways (steam, electric or other motive power at crossing only) | “A” | 
| E, H or L | Minor railways (at crossing only | “B” | 
| E or H | Under all conditions not required to be grade “A” except supply cables treated as specified in Rule 57.8 | “B” | 
| E or L | Under all conditions not required to be Grade “A” or “B” | “C” | 
| Supply cables treated as specified in Rule 57.8 | Under all conditions | “C” | 
| Major Class C | Class E or H circuit | “A” | 
| Minor Class C | Class E or H circuits | “B” | 
| C | Major railways (at crossing only) | “B” | 
| C | Class L circuits of more than 750 volts | “C” | 
| C | Supply cables treated as specified in Rule 57.8 | “F” | 
| C | Under all conditions not required to Grade “A,” “B,” or “C” | “F” | 
Note: Rule 57.8 specifies bonding and grounding of sheath and messenger of supply cables.
Strikeout and Underline Version
Table 3
| Table 3 Grades of Construction | ||
| Class of Circuits involved at upper level | Other facilities at lower level at crossing, conflicts or on poles jointly used | Grade of construction to be used at upper level | 
| E or H | 
 | “A” | 
| E, H or L | Major railways (steam, electric or other motive power at crossing only) | “A” | 
| E, H or L | Minor railways (at crossing only | “B” | 
| E or H | Under all conditions not required to be grade “A” except supply cables treated as specified in Rule 57.8 | “B” | 
| E or L | Under all conditions not required to be Grade “A” or “B” | “C” | 
| Supply cables treated as specified in Rule 57.8 | Under all conditions | “C” | 
| 
 | Class E or H circuit | “A” | 
| 
 | 
 | 
 | 
| C | Major railways (at crossing only) | “B” | 
| C | Class L circuits of more than 750 volts | “C” | 
| C | Supply cables treated as specified in Rule 57.8 | “F” | 
| C | Under all conditions not required to Grade “A,” “B,” or “C” | “F” | 
Note: Rule 57.8 specifies bonding and grounding of sheath and messenger of supply cables.
Final Version
Table 3
| Table 3 Grades of Construction | ||
| Class of Circuits involved at upper level | Other facilities at lower level at crossing, conflicts or on poles jointly used | Grade of construction to be used at upper level | 
| E or H | Class C Circuits | “A” | 
| E, H or L | Major railways (steam, electric or other motive power at crossing only) | “A” | 
| E, H or L | Minor railways (at crossing only | “B” | 
| E or H | Under all conditions not required to be grade “A” except supply cables treated as specified in Rule 57.8 | “B” | 
| E or L | Under all conditions not required to be Grade “A” or “B” | “C” | 
| Supply cables treated as specified in Rule 57.8 | Under all conditions | “C” | 
| Class C | Class E or H circuit | “A” | 
| C | Major railways (at crossing only) | “B” | 
| C | Class L circuits of more than 750 volts | “C” | 
| C | Supply cables treated as specified in Rule 57.8 | “F” | 
| C | Under all conditions not required to Grade “A,” “B,” or “C” | “F” | 
Note: Rule 57.8 specifies bonding and grounding of sheath and messenger of supply cables.