Rule 54.6-D3
54.6-D3) Runs 18 Inches From Pole Centerline: Vertical conductors may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17, and at a distance of more than 18 inches from the center line of any pole provided that such conductors are suitably insulated and covered by suitable protective covering or by securely supported impregnated fiber conduit without metal conduit. Such conductors shall be located outside of the climbing and working spaces and shall not pass between conductors of different ownership except between the pole pair and at a clearance therefrom of no less than 6 inches.
Strikeout and Underline Version
Rule 54.6-D3
54.6-D3)
Runs 18
Inches From Pole Centerline: Vertical conductors may be installed with less
than the radial clearances between conductors, specified in Table 2, Cases 16
and 17, and at a distance of more than 18 inches from the center line of any
pole provided that such conductors are suitably insulated and covered by
suitable protective covering or by securely supported impregnated fiber
conduit without metal conduit. Such
conductors shall be located outside of the climbing and working spaces and
shall not pass between conductors of different ownership except between the
pole pair and at a clearance therefrom of no less than 6 inches.
Final Version
Rule 54.6-D3
54.6-D3) Runs 18 Inches From Pole Centerline: Vertical conductors may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17, and at a distance of more than 18 inches from the center line of any pole provided that such conductors are suitably insulated and covered by suitable protective covering. Such conductors shall be located outside of the climbing and working spaces and shall not pass between conductors of different ownership except between the pole pair and at a clearance therefrom of no less than 6 inches.