Original Version
Rule 86.4-A1
86.4-A1) Over, Across or Along Public Thoroughfares: Minimum clearance shall not be less than 18 feet (Table 1, Case 3, Column A).
EXCEPTIONS:
a) A minimum clearance of 16 feet if permitted over an entrance to or exit from industrial or commercial premises.
b) A minimum clearance of 14 feet is permitted over private residential premises.
c) Clearance of overhead guys along public thoroughfares, above ground which is not normally accessible to vehicles, may be less than as specified in Table 1, Column A, Cases 3 and 4 (18 feet and 15 feet respectively), but shall not be less than 8 feet.
Strikeout and Underline Version
Rule 86.4-A1
86.4-A1) Over, Across or Along Public Thoroughfares: Minimum clearance shall not be less than 18 feet (Table 1, Case 3, Column A).
EXCEPTIONS:
a) A minimum clearance of 16 feet if permitted over an entrance to or exit from industrial or commercial premises.
b) A minimum clearance of 14 feet is permitted over an entrance to or exit from private residential premises.
c) Clearance of overhead guys along public thoroughfares, above ground which is not normally accessible to vehicles, may be less than as specified in Table 1, Column A, Cases 3 and 4 (18 feet and 15 feet respectively), but shall not be less than 8 feet.
Final Version
Rule 86.4-A1
86.4-A1) Over, Across or Along Public Thoroughfares: Minimum clearance shall not be less than 18 feet (Table 1, Case 3, Column A).
EXCEPTIONS:
a) A minimum clearance of 16 feet if permitted over an entrance to or exit from industrial or commercial premises.
b) A minimum clearance of 14 feet is permitted over an entrance to or exit from private residential premises.
c) Clearance of overhead guys along public thoroughfares, above ground which is not normally accessible to vehicles, may be less than as specified in Table 1, Column A, Cases 3 and 4 (18 feet and 15 feet respectively), but shall not be less than 8 feet.