Original Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
a)
0-7,500 Volts in Triangular Configuration:
A single conductor of a circuit of 0-7,500 volts may be attached at
the top of a pole provided the
other conductors of the same circuit are on a crossarm and are not less than 2 feet vertically below the level of such single conductor, except that
such a 2-foot vertical
separation is not required for dead-ended conductors.
Where this triangular configuration
is used, all conductors of other circuits on crossarms on the pole shall be not
less than 4 feet below the level of the lower conductors of the pole-top
circuit and conductors of 0-750 volts in rack construction shall conform to the
requirements of Rule 54.9-E.
b) More Than 7,500 Volts: A single conductor of a circuit of more than 7,500 volts may be
attached directly to the top of a pole or to a crossarm at
the top of a pole at a distance less than as specified in Table 1,
Case 8, provided no apparatus carried on the pole is connected to the circuit
so arranged except lightning arresters, a pole-top switch, or a transformer.
Where a transformer is connected
to a circuit so arranged, a
vertical clearance of not less than 30
inches shall be maintained between the primary conductor directly above and the
un-energized metal parts of the transformer, as specified in Rule, 58.3-B3e.
Where this
construction is used, all conductors of other circuits on the pole shall be not
less than 6 feet below the
pole-top conductor except that in rural districts the conductors of a 0- 750 volt secondary circuit may be not less
than 4 feet below the conductor
level of such a primary circuit
by means of which the secondary is applied.
The dead ending of a conductor at top
of pole under these provisions is optional.
Strikeout and Underline Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
a)
0-7,500 Volts in Triangular Configuration:
A single conductor of a circuit of 0-7,500 volts may be attached at
the top of a pole provided the
other conductors of the same circuit are on a crossarm and are not less than 2 feet vertically below the level of such single conductor, except that
such a 2-foot vertical
separation is not required for dead-ended conductors. Where this triangular configuration
is used, all conductors of other circuits on crossarms on the pole shall be not
less than 4 feet below the level of the lower conductors of the pole-top
circuit and conductors of 0-750 volts in rack construction shall conform to the
requirements of Rule 54.9-E.
b) More Than 7,500 Volts: A single conductor of a circuit of more than 7,500 volts may be
attached directly to the top of a pole or to a crossarm at
the top of a pole at a distance less than as specified in Table 1,
Case 8, provided no apparatus carried on the pole is connected to the circuit
so arranged except lightning arresters, a pole-top switch, or a transformer.
Where a transformer is connected
to a circuit so arranged, a
vertical clearance of not less than 30
inches shall be maintained between the primary conductor directly above and the
un-energized metal parts of the transformer, as specified in Rule, 58.3-B3e. Where this
construction is used, all conductors of other circuits on the pole shall be not
less than 6 feet below the
pole-top conductor except that in rural districts the conductors of a 0- 750 volt secondary circuit may be not less
than 4 feet below the conductor
level of such a primary circuit
by means of which the secondary is applied. The dead ending of a conductor at top
of pole under these provisions is optional.
Clearance Between a Single Conductor and Center Line of Pole: A single conductor of a circuit may be attached directly to the top
of a pole or to a crossarm at the top of a pole at a distance less than as specified in Table 1, Case 8. Where a transformer(s) or similar apparatus is
connected to a circuit so
arranged, a vertical clearance
of not less than 30 inches shall be maintained between its un-energized metal
parts and the primary conductor directly above.
Where this construction is used, no
conductors of other circuits on the pole shall be less than 6 feet below the
pole-top conductor.
EXCEPTION:
In rural districts this
clearance may be reduced to 4 feet when the primary
circuit supplies a 0-750 volt
circuit below.
For pole-top triangular and vertical construction without the use of wood crossarms see Rule 54.11.
Final Version
Rule 54.4-D8
54.4-D8) At Top of Pole:
Clearance Between a Single Conductor and Center Line of Pole: A single conductor of a circuit may be attached directly to the top of a pole or to a crossarm at the top of a pole at a distance less than as specified in Table 1, Case 8. Where a transformer(s) or similar apparatus is connected to a circuit so arranged, a vertical clearance of not less than 30 inches shall be maintained between its un-energized metal parts and the primary conductor directly above.
Where this construction is used, no conductors of other circuits on the pole shall be less than 6 feet below the pole-top conductor.
EXCEPTION: In rural districts this clearance may be reduced to 4 feet when the primary circuit supplies a 0-750 volt circuit below.
For pole-top triangular and vertical construction without the use of wood crossarms see Rule 54.11.