Original Version
Rule 54.4-C1c
54.4-C1c)
Triangular and Vertical Configuration:
Crossarms used to support conductors of a circuit at different levels (as in
triangular or vertical configuration) need not be spaced as in Table 2, Cases 9
to 13, but may be arranged so that the vertical separation of conductors of the
same circuit shall be not less than the pin spacing of Table 2, Case 15
Rule 54.4-D8
applies for pole-top triangular construction involving one circuit.
Where circuits are installed in
vertical or triangular configuration with vertical conductor separations less
than as specified in Table 2, Cases 9 to 13, not more than two circuits shall
be installed on the same crossarms and the conductors of both circuits shall be
arranged in identical physical configuration on opposite sides of pole except
at points of transportation. In the
event different voltage classifications are involved, the vertical separation
of the conductors shall be not less than the pin spacing for the highest voltage
concerned.
Strikeout and Underline Version
Rule 54.4-C1c
54.4-C1c)
Triangular and Vertical Configuration On
Different Crossarms On the Same Pole: Crossarms used to support conductors of a
circuit at different levels (as in triangular or vertical configuration) need
not be spaced as in Table 2, Cases 9 to 13, but may be arranged so that the
vertical separation of conductors of the same circuit shall be not less than
the pin spacing of Table 2, Case 15Rule 54.4-D8
applies for pole-top triangular construction involving one circuit.Where circuits are installed on
crossarms in vertical or triangular configuration with vertical conductor
separations less than as specified in Table 2, Cases 9 to 13, not more than two
circuits shall be installed on the same crossarms and the conductors of both
circuits shall be arranged in identical physical configuration on opposite
sides of pole except at points of transportation. In the event When different voltage classifications
are involved, the vertical separation of the conductors shall be not less than
the pin spacing for the higherst voltage concerned.
For pole-top triangular and vertical
construction without the use of wood crossarms see Rule 54.11.
Final Version
Rule 54.4-C1c
54.4-C1c)
Triangular and Vertical Configuration On
Different Crossarms On the Same Pole: Crossarms used to support conductors of a
circuit at different levels (as in triangular or vertical configuration) need
not be spaced as in Table 2, Cases 9 to 13, but may be arranged so that the vertical
separation of conductors of the same circuit shall be not less than the pin
spacing of Table 2, Case 15
Where circuits are installed on
crossarms in vertical or triangular configuration with vertical conductor
separations less than as specified in Table 2, Cases 9 to 13, not more than two
circuits shall be installed on the same crossarms and the conductors of both
circuits shall be arranged in identical physical configuration on opposite
sides of pole except at points of transportation. When different voltage classifications are
involved, the vertical separation of the conductors shall be not less than the
pin spacing for the higher voltage.
For pole-top triangular and vertical
construction without the use of wood crossarms see Rule 54.11.