General Order 128
 Section III
 Requirements for Supply Systems
34.2    Equipment in Manholes, Vaults, Rooms and Other Enclosures
 
Equipment shall be so arranged as to provide reasonable accessibility 
to personnel and working space for the safe operation, maintenance, and replacement 
of said equipment.
   
    
    
A.    Fused Devices
           
    
Fused devices shall be so located that they are readily 
accessible and may be safely operated and re–fused and so that the blowing
of the fuse will not endanger persons.
         
        
B.    Sectionalizing Switches
                       
    
Sectionalizing switches shall be so located that they
may be operated, maintained, or replaced from a readily and safely accessible 
place.
 They shall be so installed that the center of the grip of the operating
handle when in its highest position will not be more than 6 1/2 feet above
the floor or other standing surface. Switches with viewing windows shall
be so installed that the center of the viewing window will be not more than
6 1/2 feet above the floor or other standing surface.
               
        
C.    Transformers
                                   
    
Transformers operating at more than 600 volts, 
other than current and potential transformers and transformers which constitute 
a component part of other apparatus and which conform to the requirements 
of such apparatus, shall be readily accessible for operation, inspection, 
maintenance, and replacement.
                     
 Transformers shall be installed in such a manner as to permit safe operation, 
maintenance, or replacement of other equipment.
                     
 Transformers installations shall be provided with means of ventilation adequate 
to prevent temperatures in excess of those at which the transformer may be 
safely operated.