General Order 128
 Section III
 Requirements for Supply Systems
 
  
34.3 
           Self–contained Surface–mounted Equipment
 
        
Equipment installed partially or completely above the ground surface
and not enclosed by a vault, room or fence shall conform to the following:
   
            
A.    Strength
           
The equipment case or enclosure shall be secured in place 
and be of sufficient strength to resist entrance or damage to the equipment 
by unauthorized persons.
         
B.    Guarding Live Parts
                       
Compartments and enclosures which will, during normal 
operation, contain exposed live parts shall be designed and installed to prevent
a person from passing a wire or other conducting material into such compartment
from the outside when it is closed. This requirement is not intended to prevent
normal work operations such as fishing ducts and installing cable.
EXCEPTION:
Pad-mounted equipment that contains
exposed live parts shall be installed to resist the passing of a wire the
equivalent of a bare number 18 AWG from the outside between the pad and the
housing of the equipment, into the compartment which contains live parts when
it is closed.
C.    Locking
                                   
Compartments and enclosures shall be made secure 
against entry by unauthorized persons by means of locks or other suitable 
means.
                     
D.    Clearance from Buildings
                                               
Equipment containing oil shall be so located
that the nearest metal parts of such equipment clear the surface of buildings
by not less than 3 feet. This clearance may be reduced to 2 feet if the building
surface is noncombustible. Equipment not containing oil need have no specific
clearance from buildings and may be incorporated into the building structure.