General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
54.8 Service Drops, 0 - 750 Volts
A. Material and Size
Supply service drops of 0 - 750 volts shall be of material
and size as specified in Table
8
and Rule 49.4–C7a
.
Note:
Resolution No. E–756 effective May 29, 1951
authorized the use of multiple conductor service drop cable with a
bare neutral conductor for service drops of 0 - 750 volts provided that
the attachment of such cable at the pole and building ends shall be by
means of an insulator.
B. Clearances above Ground, Buildings, Etc.
The vertical clearances of supply service drops above
ground, buildings, etc., shall be not less than the minimum clearances
specified in Rule 37
, Table 1, Column B
, with the following modifications:
(1) Above Public Thoroughfares: Service drop conductors shall
have a vertical clearance of not less than 18 feet above public thoroughfares,
except that this clearance may grade from 18 feet at a position not more
than 12 feet horizontally from the curb line to a clearance of not less
than 16 feet at the curb line, provided the clearance at the centerline
of any public thoroughfare shall in no case be less than 18 feet. Where there
are no curbs the foregoing provisions shall apply using the outer limits
of possible vehicular movement in lieu of a curb line.
(2) Above Private Thoroughfares and Other Private Property:
a) Industrial or Commercial Premises: Over private driveways,
lanes, or other private property areas accessible to vehicles on premises
used for industrial or commercial purposes, service drops shall have a
vertical clearance of not less than 16 feet.
b) Residential Premises: Over private driveways or lanes or
other private property areas accessible to vehicles on premise used for
residential purposes only, service drops shall have a vertical clearance
not less than 12 feet.
EXCEPTION: This clearance may be reduced for insulated services that conform with Rule 20.9-G to not less than 10 feet
Note:
Revised January 21, 1992 by Resolution SU-10.
(3) Above Ground in Areas Accessible to Pedestrians Only:
Over areas accessible
to pedestrians only service drops shall be maintained at a vertical
clearance of not less than 12 feet.
EXCEPTION: This clearance may be reduced for insulated services that conform
with Rule 54.8–A
, to not less than 8 feet 6 inches.
Note: Revised January 21, 1992 by Resolution SU–10 and January 13, 2006 by Decision No. 05-01-030
(4) From Buildings and Structures: Service drops should be arranged
so as not to hamper or endanger workers and firefighters while performing
their duties.
a) Vertical Clearances: Service drop vertical clearances shall
be maintained over all portions of buildings and structures as required
by Table 10
.
Note:
Revised October 2, 1951 by Resolution No. E–762
; January 6, 1968 by Decision No. 73455; and January 21, 1992, by Resolution
SU–10.
b) Horizontal Clearances: Service drops are not required to
clear buildings by any specific horizontal distance.
EXCEPTION: A horizontal distance of not less than 3 feet should
be maintained around fire escapes, exits, windows or doors.
Note: Revised January 21, 1992 by Resolution
SU–10.
Table 10: Minimum Allowable Clearance of Service Drops of 0 - 750 Volts from Buildings |
||
|
Minimum Clearance from Buildings |
|
Weather Resistant |
Insulated Conductors |
|
Vertical Clearances Above: |
||
1) All portions of buildings including metallic or non–metallic cornice, decorative appendage, eaves, roof or parapet wall of the building served. |
8 Feet |
|
2) Metallic or non–metallic non–walkable overhang, patio cover or other structure. |
8 Feet |
|
3) Other buildings on the same premises. |
8 Feet |
2 Feet |
4) Buildings on other premises. |
8 Feet |
8 Feet (c) |
Horizontal & Radial Clearances: |
||
1) From fire escapes, exits, windows and doors. |
3 Feet |
3 Feet |
a) Minimum clearance of 0.5 inches.
b) The point of attachment of the service drop for industrial and commercial premises is not to be more than 18 inches back of the front face of the building wall facing the pole line from which the service drop originates.
c) Reduce to 2 feet for non–metallic roofs when roof slope exceeds 9 inches of rise per 12 inches of run (see sketch ).
Note: Revised September 18, 1967 by Decision No. 72984; January 6, 1968 by Decision No. 73455; July 22, 1968 by Decision No. 74342; January 21, 1992, by Resolution SU–10; November 6, 1992 by Resolution SU–15 and January 13, 2006 by Decision No. 05-01-030
(5) Over Swimming Pools: (See
Rule 54.4–A3
and
Figure 54–1
).
Note: Added January 2, 1962 by Resolution No.
E–1109 and Revised November 21, 1990 by Resolution SU–6.
C. Clearances between Supply Service Drops and
Other Conductors
The clearances of supply service drop conductors from other conductors
shall be not less than the minimum clearances specified in
Rule 38
, Table 2, Column D
, with the following modifications:
(1) From Fire Alarm or Other Communication Line Conductors:
a) Crossings in Spans: At crossings in spans, supply service drop
conductors may have a clearance of less than 48 inches (
Table 2, Case 3, Column D; and Case 4, Column C
) but not less than 24 inches above any communication line conductors
or below communication line conductors not supported on a messenger, provided
the crossing is 6 feet or more from any pole which does not support both
conductors involved in the crossing (See
App. G, Figure 42
).
b) Supported on the Same Pole: Supply service drop conductors, other than those on a pole–top clearance attachment, may have a clearance of less than 48 inches (Table 2, Case 8, Column D; and Case 9, Column C ) above or below communication line conductors supported by the same pole and not on a messenger provided such clearance is 6 feet or more from any pole which does not support both conductors involved, and provided clearances at least equal to those shown in Table 11 are maintained.
Table 11: Minimum Radial Clearance between Supply Service Drop Conductors and Communication Line Conductors Not on Messengers |
||
Radial Distance of Crossing from Supporting Pole (Feet) |
Minimum Radial Clearance (Inches) |
|
From Police and Fire Alarm Conductors |
From Other Communication Conductors |
|
5 or less |
6 |
12 |
10 or less, but more than 5 |
9 |
18 |
15 or less, but more than 10 |
15 |
24 |
20 or less, but more than 15 |
21 |
24 |
More than 20 |
24 |
24 |
Supply service drop conductors may have a clearance of less than
48 inches (as specified in
Table 2, Case 8, Column D; and Case 9, Column C
) but not less than 24 inches above and laterally from communication
line conductors supported on a messenger by the same pole provided such
clearance is 6 feet or more from any pole which does not support both
conductors. The vertical clearances of not less than 24 inches above or
48 inches below communication conductors supported on messengers are not
required where the supply service drop conductors are 24 inches or more
horizontally from the vertical plane of the communication messenger (see
App. G, Figure 42
).
(2) On Clearance Crossarms: Supply service drops may be supported
on a clearance crossarm at a vertical distance less than 48 inches (specified
in Table 2, Case 8, Column
D, and Case 9, Column C)
but not less than 24 inches above or below either supply circuits
of 0 - 750 volts or communication circuits not supported on a messenger,
or above communication or supply circuits which are supported on a messenger,
provided the supply service drop unprotected conductors are at least
25 inches horizontally from the centerline of the pole or are attached
to suitable brackets (at least 25 inches from center line of pole) on
each end of the clearance arm and carried on the underside of the clearance
arm from end to end in fiber or plastic conduit or under wood protective
covering as specified in Rule 54.6–C
. The installation of service drops in accordance with this rule will
not entail any change in the communication conductors supported on the pole
(see App. G, Figure
40
).
Note: Revised
June 7, 1965 by Decision No. 69071.
(3) On Pole Top Extensions: Supply service drops may be carried
in a clearance crossing on pole top extensions or brackets above either
supply circuits of 0 - 750 volts or communications circuits, with a vertical
conductor clearance less than 48 inches (
Table 2, Case 8, Column D; Case 9, Column C
) but not less than 2 feet provided the service drop conductors clear
the centerline of the pole (projected) not less than 25 inches horizontally,
and also provided the service drop conductors clear the outside pin
position conductors of the other circuit not less than 2 feet. Where,
in addition to the pole top bracket or extension, the supply service
drop conductors are supported on a bracket on the end of the other line
crossarm, a clearance of not less than 12 inches will be permitted at
the points of crossing of line conductors in the outside pin positions.
In such construction the crossarm of the extension shall be of wood. The
installation of service drops in accordance with this rule will not entail
any change in the communication conductors supported on the pole (see
Appendix G, Figure 41
).
(4) From Communication Service Drops: The radial clearance
between supply service drop conductors and communication service drop
conductors may be less than 48 inches as specified in
Table 2, Column C, Cases 4 and 9; Column D, Cases 3 and 8
, but shall be not less than 24 inches. Where within 15 feet of the
point of attachment of either service drop on a building, this clearance
may be further reduced but shall be not less than 12 inches.
(5) Above Trolley Contact Conductors: Service drops may be
installed above trolley contact conductors, including messenger in catenary
construction, at a vertical distance of not less than 4 feet, provided
the service drops clear the top of rails a vertical distance of not less
than 26 feet where the railroad crossed transports standard freight cars,
or not less than 23 feet where the railroad does not transport standard
frights cars (see Rule 74.4–B1
).
(6) From Conductors of 750 - 7,500 Volts: Service drops may
cross above or below line conductors of 750 - 7,500 volts supported on
the same pole at clearances less than specified in
Table 2, Case 10, Column D
, provided such drops shall be not less than 2 feet vertically or 1
foot horizontally from the supply line conductors.
D. Clearance from Other Poles
The clearance between service drop conductors and the centerline
of any pole not supporting them shall be not less than 22 1/2 inches
( Rule 32.3
). In case the pole involved in this clearance is within 10 feet of
a pole supporting the service drop, this clearance may be less than 22 1/2
inches but shall be not less than 15 inches.
(1) From Nonclimbable Street Lighting or Traffic Signal Poles or
Standards: Supply service drops of 0 - 750 volts passing (unattached)
nonclimbable street lighting and traffic signal poles or standards including
mastarms, brackets and lighting fixtures, shall clear a radial distance
of 12 inches as specified in
Table 1, Case 10, Column B
, except when the drops are mechanically protected from abrasion by
materials specified in Rule 22.8
. Such mechanical protection shall extend not less than 15 inches in
each direction along the drop from centerline of pole, standard, attaching
mastarm or fixture, whether passing above, below or alongside. The drops
shall be installed in such a manner so as not to interfere with light distribution
from lighting fixtures and shall not hamper workmen when changing lamps
or maintaining equipment.
Note: Added January 8, 1980 by Decision No. 91186 and
revised March 9, 1988 by Resolution E–3076.
E. Clearances from Conductors on Combination
Arms
In combination arm construction the following clearances are required
between service drop conductors of 0 - 750 volts and the conductors of
750 - 7,500 volts:
(1) 36–Inch Minimum Pole Pin Position Separation: Where conductors
of the two voltage classifications are supported on opposite ends of
a crossarm with a minimum horizontal separation of 36 inches between pole
pin positions, service drops which are run directly from such crossarm
shall not cross conductors of the 750 - 7,500 volt classification on the
same arm.
(2) 42–Inch Minimum Pole Pin Position Separation:
a) Services from Line Arms: Where conductors of the two voltage
classifications are supported on opposite ends of the crossarm with
a minimum horizontal separation of 42 inches between pole pin positions,
service drops may be run directly from the 0 - 750 volt portion of a line
arm and may cross below conductors of 750 - 7,500 volts on the same arm.
Under these conditions the vertical separation at the point of crossing
shall be not less than 2 feet, and the point of crossing shall be not less
than 6 feet radially from the centerline of pole.
b) Services from Buck Arms: Where conductors of the two voltage
classifications are supported on opposite ends of the buck arm with
a minimum horizontal separation of 42 inches between pole pin positions
and not less than 2 feet vertical separation between line arm conductor
level and buck arm conductor level, service drops may be run from line
buck arms or service buck arms, provided:
Such service drops shall clear conductors of 750 - 7,500 volts
by not less than 2 feet vertically at the point of crossing;
Such service drops shall not pass through the climbing space specified
in Rule 54.7–A3c
;
Such service drops shall not cross under the 750 - 7,500 volt end
of the line arm within the third pin position; and;
Where such service drops are run from double buck arms, or from
single buck arms installed on the side of the pole below the 750 - 7,500
volt portion of the related line arm, the pole–pin position on the 750
- 7,500 volt end of the line arm shall be left vacant.
F. From Racks
Service drops may be run directly from low voltage racks on poles.
Where multiple conductor service cable is used, the cable grip shall
be attached to the neutral insulator of the rack on the pole or suitable
insulation shall be used between the point of attachment on the rack or
pole and the surface of the cable, except where the rack hardware is effectively
grounded through the medium of a metal pole.
G. Service / Clearance Poles (See
Rule 22.6-F
For Definition)
(1)
Service / Clearance Poles Shall Support Only:
a) 0 - 750 Volt conductors (See Rule 54.8–G2 )
b) Service drops
c) Associated risers and runs
d) Associated guys
e) Lighting and its associated equipment
f) Communication facilities
(2)
Construction Requirements:
a) All supply service drop strength requirements may be applied to 0 - 750 volt conductors (secondary) installed under this Rule.
b) Span lengths shall not exceed 150 feet.
c) Supply conductors (secondary) installed between service / clearance poles shall meet the 0 - 750 volt conductor clearance requirements of Rule 37 , Table 1, Column D and Rule 38 , Table 2, Column D
d) Multiple service drops, risers and street lights may be served
from 0 - 750 volt conductor (secondary) installed under this Rule.