Original General Order
95
Section
V
Detailed Construction Requirements for Supply Lines
(Class H, L
and T Circuits)
58.2 Street Lighting Equipment
A. Circuit Voltage
Constant current series lighting circuits supplied from transformers or devices having an open circuit output voltage of more than 750 volts, except those circuits supplied from transformers or devices having a normal full load output voltage of 750 volts or less which transformers are equipped with effective protective devices to prevent the continued existence of open-circuit voltage on the circuit, shall be classified as circuits of more than 750 volts.
Constant current series lighting circuits which conform to the specifications for circuits of 0-750 volts may be installed and treated as circuits of more than 750 volts provided any circuit so treated in any respect is consistently so treated throughout its entirety.
B. Clearances
(1) Above Ground: No part of street lighting equipment shall be less than 20 feet above thoroughfares except for lamps supported on brackets or fixtures which do not extend more than 48 inches from the face of pole or street side of curb, in which case the clearances may be reduced to 15 feet, provided the voltage does not exceed 750 volts (see App, G, Fig. 56).
(2)
Above Railways and Trolley Lines: No
part of street lighting equipment which is less than 8 ½ feet horizontally from
center line of tracks of railroads not operated by overhead trolley shall be
less than 25 feet above such tracks.
No part of street lighting
equipment which is less than 8 ½ feet horizontally from center line of tracks
or from the nearest trolley contact conductor shall be less than 4 feet above the
level of the trolley contact conductor or less than 23 feet or 26 feet above
running above surfaces used by trolley cars or coaches depending upon the
location of the contact conductors as required by Rule 74.4-B1.
Those parts of street lighting
equipment which are 8 ½ feet or more horizontally from center line of any
railroad track or any trolley contact conductor shall be not less than 20 feet
above the surface of the thoroughfare, except as provided in Rule 58.2-B1 (see
App. G, Fig. 56).
(3) From Conductors
a) Messengers and Cables: All parts of street light drop wires, street lamps, and their supporting fixtures (including rods, braces, and guys) shall not be less than 1 foot above or 2 feet below the level of messengers or conductors supported by messengers. These vertical clearance requirements shall not apply to those parts of such street lighting equipment which are 2 feet or more horizontally from the vertical plane messengers, conductors supported by messengers, and metal boxes.
b) Conductors not supported by Messengers: All parts of street light drop wires, street lamps, and their supporting fixtures (including rods, braces and guys) shall not be less than 1 foot radially from all unprotected conductors not supported on messengers (including lead wires and taps) except the lead wires supplying the street within 24 inches of their points of entrance to the street lighting equipment.
(4) From Poles: All exposed metal parts of lamps and all such parts of their supports, unless insulated from the parts carrying current, shall be maintained not less than 20 inches from the surface of wood poles, except at pole tops. This rule shall not apply if the voltage of the circuit from which the lamp is supplied does not exceed 750 volts.
C. Lead wires
Unprotected conductors from one level on a pole structure to another level or to street lighting equipment shall not pass within a climbing or working space, and shall not pass within a climbing or working space, and shall not pass through any other circuit except between pole pin positions.
Such unprotected conductors shall clear the conductors of other circuits by distances as specified in Rule 54.6-A.
Where the distance between levels is in excess of 12 feet and such unprotected conductors pass between the pole pair of conductors of any other circuit, additional supports shall be installed so that the maximum length of conductor between supports is not more than 12 feet.
Unprotected leads to street lighting equipment shall be maintained at not less than the clearances above railroads, thoroughfares and ground specified for street lighting equipment in Rule 58.2-B.
D. Insulators in Supports
Where a street lighting fixture is supported by a span wire, strain insulators shall be inserted in the span wire on both sides of the fixture not more than 9 feet nor less than 6 feet from the structures supporting the span wire; except that, where such span wire is used as a trolley for the purpose of drawing the fixture to the pole, the strain insulator at the service end may be located a distance of not less than 15 inches from the center line of pole.
Where metallic ropes or chains are used for the suspension of street lamps, said ropes or chains shall be effectively insulated from current carrying parts of equipment and of such length that when the lamp is in its normal position the lower end of the chain or rope will not be less than 8 feet from ground, or a strain insulator shall be inserted in the free end of the rope or chain at a point not less than 7 ½ feet from the ground when the lamp is in its normal operation. Metallic ropes or chains shall be arranged so that they do not establish a metallic conducting path around a span wire-wire sectionalizing insulator. In case this construction will not permit the lamp to be lowered sufficiently for trimming purposes, a nonmetallic rope shall be used.
See App. G, Fig. 56.
E. Lighting Units on Transformer Poles
Where a lamp is installed above a transformer or switch, a minimum vertical separation of 4 feet from any portion of the transformer or switch and the lighting unit shall be maintained.
Where a lamp is installed below a transformer, any portion of the lighting equipment shall clear all supply equipment a minimum distance of 1 foot.
F. Cutouts
Suitable devices shall be provided by which each street lamp on series circuits of more than 750 volts may be safely and entirely disconnected from the circuit, before the lamps are handled, unless the lamps are worked on from wood poles or from suitable insulating stools, platforms or tower wagons. Exempted from this provision are lamps such as incandescent lamps which in themselves present a noncurrent-carrying surface which may be utilized as a handle in removing them from their support.
G. Exceptions
Lighting units supported on ornamental posts and supplied from underground sources are not included herein.