Original General Order 95
Section
VIII
Detailed Construction Requirements for
Communication Lines
(Class C Circuits)
86.8 Guy Insulators
Insulators which sectionalize guys shall conform to the following specifications based on the highest voltage of supply conductors carried at the level on the pole, tower, structure or crossarm nearest which the guy is attached and adequate for the voltage of supply circuits through which the guy passes.
A. Material
Insulators used in guys on communication lines shall be porcelain, glass or other equally suitable material.
B. Strength (see Rule 44, Table 4 and Rule 49.5-B)
C. Voltage Requirements
Insulators used in guys on communication lines shall be so designed that their dry flashover voltage is not more than 75% of their puncture voltage at the operating frequencies of supply lines to which guys are exposed.
Insulation used in guys on communication lines shall have a dry flashover voltage not less than as specified in Table 16 when tested in accordance with the Standards (No. 41, March, 1930) of the American Institute of Electrical Engineers under the maximum mechanical loadings specified by this Order for the guy construction involved.
Table 16 Guy Insulator Flashover Voltage |
|
Nominal voltage of circuits nearest point of attachment |
Dry flashover voltage of insulation |
0-7500 volts |
15,000 volts |
7500-17,500 volts |
Double the circuit voltage |
Over 17,500 volts |
35,000 volts |