Rule 54.8-B4a
54.8-B4a)
Industrial
and Commercial premises: On premises used for industrial or commercial purposes service
drops shall be maintained
at a vertical clearance of not less than 8 feet over all or any portions of buildings and structures,
except that service drops of 0-300 volts may be less than 8 feet, but not less than 12
inches, above the cornice, decorative appendage, eave, roof or parapet wall of
the building served provided:
The current carrying service
conductors are insulated for the voltage being supplied (see Rule 20.8-F), and
the point of attachment of the service drops is not more than 18 inches back of
the front face of the building wall facing the pole line from which the service
drops originate.
Service drops are not required to clear buildings any specified horizontal distance but shall be so installed that they clear fire escapes exits,
windows, doors and other points at which human contact might be expected a
horizontal distance of not less than 3 feet.
Where service drop crosses
over metallic or non-metallic nonwalkable overhang or patio cover vertical
clearance may be less than 8 feet, but not less than 24 inches providing such
service drops consist of abrasion-resistant cables having a grounded metallic
sheath and are insulated for the voltage being supplied.
Strikeout and Underline version
Rule 54.8-B4a
54.8-B4a)
Industrial
and Commercial premises: On premises used for industrial or commercial purposes service
drops shall be maintained
at a vertical clearance of not less than 8 feet over all or any portions of buildings and structures,
except that service drops of 0-300 volts may be less than 8 feet, but not less than 12
inches, above the cornice, decorative appendage, eave, roof or parapet wall of
the building served provided:
The current carrying service
conductors are insulated for the voltage being supplied (see Rule 20.8-F
20.8-G), and
the point of attachment of the service drops is not more than 18 inches back of
the front face of the building wall facing the pole line from which the service
drops originate.
Service drops are not required to clear buildings any specified horizontal distance but shall be so installed that they clear fire escapes exits,
windows, doors and other points at which human contact might be expected a
horizontal distance of not less than 3 feet.
Where service drop crosses
over metallic or non-metallic nonwalkable overhang or patio cover vertical
clearance may be less than 8 feet, but not less than 24 inches providing such
service drops consist of abrasion-resistant cables having a grounded metallic
sheath and are insulated for the voltage being supplied.
Final Version
Rule 54.8-B4a
54.8-B4a)
Industrial
and Commercial premises: On premises used for industrial or commercial purposes service
drops shall be maintained
at a vertical clearance of not less than 8 feet over all or any portions of buildings and structures,
except that service drops of 0-300 volts may be less than 8 feet, but not less than 12
inches, above the cornice, decorative appendage, eave, roof or parapet wall of
the building served provided:
The current carrying service
conductors are insulated for the voltage being supplied (see Rule 20.8-G), and
the point of attachment of the service drops is not more than 18 inches back of
the front face of the building wall facing the pole line from which the service
drops originate.
Service drops are not required to clear buildings any specified horizontal distance but shall be so installed that they clear fire escapes exits,
windows, doors and other points at which human contact might be expected a
horizontal distance of not less than 3 feet.
Where service drop crosses
over metallic or non-metallic nonwalkable overhang or patio cover vertical
clearance may be less than 8 feet, but not less than 24 inches providing such
service drops consist of abrasion-resistant cables having a grounded metallic
sheath and are insulated for the voltage being supplied.