General Order 64-A
Section X
Supply And Communication Lines In Crossings Or Conflicts
104.1 Additional Insulation.
Where grounded pins are used at crossings
(non-grounded construction being used at other parts of the line), the
insulators used on such metal or grounded supports shall have a ratings of 25%
greater than the flash-over voltage values of the line insulators except where
these values exceed those specified in Table 9, Rule 55.3, by 50%. As an alternative, the conductors at their
points of attachment, where suspension insulators are used, may be protected by
arcing shields.