General Order 64-A
Appendix
D
Typical Communication Line Construction
Table 27 GUY REQUIREMENTS FOR OPEN WIRE COMMUNICATION LINES IN GRADE “F” CONSTRUCTION Dead-End Poles |
|||
Ultimate number of wires involved |
Minimum specifications Number and Ultimate Strength of guys |
||
½ |
¾ |
1 |
|
1 or 2 |
1 – 1,800 |
1 – 1,600 |
1 – 1,600 |
3 to 6 |
1 – 6,000 |
1 – 5,100 |
1 – 5,100 |
7 to 10 |
1 – 11,500 |
1 – 6,800 |
1 – 6,000 |
11 to 20 |
2 – 9,000 |
2 – 6,800 |
1 – 11,500 |
21 to 30 |
2 – 9,000 |
2 – 11,500 |
2 – 9,000 |
1 – 11,500 |
|||
31 to 40 |
3 – 11,500 |
2 – 9,000 |
2 – 11,500 |
1 – 11,500 |
Note: = ratio of lead over height. These values are ultimate strengths in pounds per square inch.
See App. G, Fig. 92, covering terms used herein. See rule 49.7-B.