General Order 64-A
Supplement Number 1
Original Version
Rule 49.4
49.4 Conductors
A.
Material
Open wire conductors shall be of
copper, copper covered steel galvanized iron or steel or other
corrosion-resisting metal, not subject to rapid deterioration.
B.
Size
The minimum sizes of wires of
various materials which shall be used for the several classes of construction
and loading are listed below. These
minimum sizes shall obtain in both urban and rural districts. Larger sizes of wire than those shown in
table will often be necessary to maintain reasonable sag and at the same time
provide the required safety factors of Rule 44, ground clearances of Table 1,
and wire clearances of Table 2.
The minimum size of wire given in
Table 7 is dependent upon spans not in excess of 150 feet. Longer spans except when specifically
designated, may be employed without increasing the size of wire, provided the
sags and conductor separations are so increased that the allowable working
tensions and conductor clearances of this order are not violated.
Table 7 Minimum Allowable Conductor Sizes (150ft. span) |
||||||
Loading and Construction grade |
Material or Type of Conductor |
|||||
Soft drawn copper |
Hard-drawn copper |
Standard Aluminum wire |
Reinforced stranded Aluminum |
Copper-covered steel or |
Galvanized iron or steel wire |
|
A.W.G |
A.W.G |
A.W.G |
A.W.G |
A.W.G |
|
|
Heavy Loading, Grade “A” |
No. 4 |
No. 6 |
No. 1 |
No. 4 |
No. 6 |
¼ in diam. strand |
Heavy Loading, Grade “B” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Heavy Loading, Grade “C” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “A” |
4 |
6 |
1 |
4 |
8 |
*¼ in diam. strand |
Light Loading, Grade “B” |
6 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “C” |
6 |
8 |
1 |
6 |
40 |
No. 9 Steel W.G. |
Other supply service drops |
10 |
10 |
------- |
------- |
12 |
------- |
Supply service drops crossing trolley wires |
8 |
10 |
------- |
------- |
12 |
------- |
All Loadings Grade “F” |
------- |
12 |
------- |
------- |
12 |
No. 14 Steel W.G. |
All loadings of communication service drops, paired wires or bronze conductors |
------- |
14 |
------- |
------- |
17 |
------- |
* Three-sixteenth-inch strand may be used upon special permission of the Railroad Commission
C. Strength
(1) Heavy Loading Districts: Conductors in Grade “A” construction and in spans exceeding 150 feet shall have a tensile strength not less than that of No. 4 A.W.G hard-drawn copper, and said conductors shall preferably be stranded.
(2)
Light Loading Districts: The
following requirements apply for various grades of construction and span
lengths.
Conductors of Grade “A”
construction in spans not exceeding 300 feet in length shall have a tensile
strength not less than No. 6 A.W.G. hard drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 6 A.W.G. soft drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 8 A.W.G. soft drawn copper, provided the voltage is
less than 750.
(3) Heavy or Light Loading Districts: Where signal or communication lines take Grade “B” or “C” classification other than at railroad crossings, a minimum size of No. 8 AWG hard-drawn copper or its equivalent in tensile strength may be used. In crossing over supply cables where Grade “C” construction is required No. 10 A.W.G. hard drawn copper or its equivalent may be used in spans not exceeding 150 feet.
(4) Conductors of Voltage Exceeding 17,000 Volts: Conductors of voltages exceeding 17,000 volts crossing conductors of less than 17,000 volts, crossing a public highway shall have a strength at least equal to No. 4 A.W.G. stranded hard-drawn copper. In lieu of this conductors carrying more than 17,000 volts shall, at the point of crossing, be supported on poles of such height and so placed that under no circumstance can the conductor of over 17,000 volts, or fall within a distance of ten feet from the surface of any public highway.
(5) Sags and Tensions: Conductor sags shall be such that under the assumed loading conditions the tension in the conductors shall not be more than one-half the breaking strength of the conductor, other than communication circuits. The minimum allowable sags for conductors calculated on this basis are given in Appendix C. The use of sags greater than allowable minimum may be desirable in order to reduce working tensions. Where sags greater than those indicated are used adequate clearance shall be provided. (See Rule 47.) Where the minimum size pins are used the conductor tensions shall be limited to 2000 pounds when applying the double arm, pin and conductor fastening provisions of Rules 49.2 and 49.3.
(6) Splices: Splices in line conductors shall be of equal or greater strength than the conductors in which they are made.
(7) Service Drops
a) Supply: The minimum sizes shall apply only where the span does not exceed 150 feet. The minimum for supply lines of like voltage and grade shall apply when the service drop is in excess of 150 feet. Supply service drops of 0-750 volts shall, in all cases, have an insulating covering equivalent to standard double braid weatherproofing.
b) Communication: Communication service drops of No. 16 AWG paired copper wire may be used provided they do not cross over supply lines, trolley contact or feeder conductors or railways.
D. Replacements (see Rule 44.2)
Strikeout and Underlined Version
Rule 49.4
49.4 Conductors
A.
Material
Open wire conductors shall be of
copper, copper covered steel, aluminum (including A. C. S. R.),
galvanized iron or steel or other corrosion-resisting metal not subject to
rapid deterioration, except that where a common primary and secondary
grounded neutral distribution system of 5000 volts or less is installed, the
following provisions shall apply:
(1) Galvanized iron or steel shall not be used as a conductor.
(2) Related phase and neutral line conductors shall be of the same material, except that the neutral conductor may be of copper where the phase conductors are of other approved material.
(3) All conductors and wires connecting the common neutral line conductor to ground shall be of copper.
B.
Size
The minimum sizes of wire of
various materials which shall be used for the several classes of construction
and loadings are listed below in Table No. 7. These minimum sizes shall obtain in both
urban and rural districts. Larger sizes
of wire than those shown in the table will often be necessary to maintain
reasonable sag and at the same time provide the required safety factors of Rule
44, ground clearances of Table No. I and wire clearances of Table No. 2.
In common primary and secondary
grounded neutral systems the common neutral line conductor shall have a minimum
area approximately not less than fifty (50) per cent of the area in circular
mills of the largest related primary phase conductor, and in no case shall have
less conductivity or mechanical strength than No. 6 A. W. G. copper.
In common primary and secondary
grounded neutral systems the size of the common neutral line conductor to be
used with related phase conductors shall be not less than those set forth in the
following table:
TABLE No. 6-A Minimum Sizes of Common Neutral Line Conductors |
|
Size of phase conductor |
Minimum size of neutral conductor |
500,000 C.M. |
4/0 |
350,000 C.M. |
3/0 |
250,000 C.M. |
2/0 |
4/0 |
1/0 |
3/0 |
1 |
2/0 |
2 |
1/0 |
3 |
1 |
4 |
2 |
6 |
4 |
6 |
6 |
6 |
This table is based upon the requirement that the common neutral line conductor shall have a minimum area of approximately fifty (50) per cent of the area of the largest related phase-conductor and that the phase and neutral conductors are of the same material. Where these are not of same material, the copper equivalents of the table shall be considered as meeting the requirements.
The minimum sizes of wire given
in Table No. 7 is dependent are based upon
spans not in excess of one hundred fifty (150) feet. Longer spans, except when specifically
designated, may be employed without increasing the size of wire, provided the
sags and conductor separations are so increased that the allowable working
tensions and conductor clearances specified in this order are not violated.
Table 7 Minimum Allowable Conductor Sizes (150ft. span) |
||||||
Loading and Construction grade |
Material or Type of Conductor |
|||||
Soft drawn copper |
Hard-drawn copper |
Standard Aluminum wire |
Reinforced stranded Aluminum |
Copper-covered steel or |
Galvanized iron or steel wire |
|
A.W.G |
A.W.G |
A.W.G |
A.W.G |
A.W.G |
|
|
Heavy Loading, Grade “A” |
No. 4 |
No. 6 |
No. 1 |
No. 4 |
No. 6 |
¼ in diam. strand |
Heavy Loading, Grade “B” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Heavy Loading, Grade “C” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “A” |
4 |
6 |
1 |
4 |
8 |
*¼ in diam. strand |
Light Loading, Grade “B” |
6 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “C” |
6 |
8 |
1 |
6 |
40 |
No. 9 Steel W.G. |
Other supply service drops |
10 |
10 |
------- |
------- |
12 |
------- |
Supply service drops crossing trolley wires |
8 |
10 |
------- |
------- |
12 |
------- |
All Loadings Grade “F” |
------- |
12 |
------- |
------- |
12 |
No. 14 Steel W.G. |
All loadings of communication service drops, paired wires or bronze conductors |
------- |
14 |
------- |
------- |
17 |
------- |
* Three-sixteenth-inch strand may be used upon special permission of the Railroad Commission
C. Strength
(1) Heavy Loading Districts: Conductors in Grade “A” construction and in spans exceeding 150 feet shall have a tensile strength not less than that of No. 4 A.W.G hard-drawn copper, and said conductors shall preferably be stranded.
(2)
Light Loading Districts: The
following requirements apply for various grades of construction and span
lengths.
Conductors of Grade “A”
construction in spans not exceeding 300 feet in length shall have a tensile
strength not less than No. 6 A.W.G. hard drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 6 A.W.G. soft drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 8 A.W.G. soft drawn copper, provided the voltage is
less than 750.
(3) Heavy or Light Loading Districts: Where signal or communication lines take Grade “B” or “C” classification other than at railroad crossings, a minimum size of No. 8 AWG hard-drawn copper or its equivalent in tensile strength may be used. In crossing over supply cables where Grade “C” construction is required No. 10 A.W.G. hard drawn copper or its equivalent may be used in spans not exceeding 150 feet.
(4) Conductors of Voltage Exceeding 17,000 Volts: Conductors of voltages exceeding 17,000 volts crossing conductors of less than 17,000 volts, crossing a public highway shall have a strength at least equal to No. 4 A.W.G. stranded hard-drawn copper. In lieu of this conductors carrying more than 17,000 volts shall, at the point of crossing, be supported on poles of such height and so placed that under no circumstance can the conductor of over 17,000 volts, or fall within a distance of ten feet from the surface of any public highway.
(5) Sags and Tensions: Conductor sags shall be such that under the assumed loading conditions the tension in the conductors shall not be more than one-half the breaking strength of the conductor, other than communication circuits. The minimum allowable sags for conductors calculated on this basis are given in Appendix C. The use of sags greater than allowable minimum may be desirable in order to reduce working tensions. Where sags greater than those indicated are used adequate clearance shall be provided. (See Rule 47.) Where the minimum size pins are used the conductor tensions shall be limited to 2000 pounds when applying the double arm, pin and conductor fastening provisions of Rules 49.2 and 49.3.
(6) Splices: Splices in line conductors shall be of equal or greater strength than the conductors in which they are made.
(7) Service Drops
a) Supply: The minimum sizes shall apply only where the span does not exceed 150 feet. The minimum for supply lines of like voltage and grade shall apply when the service drop is in excess of 150 feet. Supply service drops of 0-750 volts shall, in all cases, have an insulating covering equivalent to standard double braid weatherproofing.
b) Communication: Communication service drops of No. 16 AWG paired copper wire may be used provided they do not cross over supply lines, trolley contact or feeder conductors or railways.
D. Replacements (see Rule 44.2)
E.
Connections.
All electrical connections shall be soldered or of such rigid mechanical design
that there will be no material increase in the ohmic resistance of the circuit.
Final Version
Rule 49.4
49.4 Conductors
A.
Material
Open wire conductors shall be of
copper, copper covered steel, aluminum (including A. C. S. R.),
galvanized iron or steel or other corrosion-resisting metal not subject to
rapid deterioration, except that where a common primary and secondary
grounded neutral distribution system of 5000 volts or less is installed, the
following provisions shall apply:
(1) Galvanized iron or steel shall not be used as a conductor.
(2) Related phase and neutral line conductors shall be of the same material, except that the neutral conductor may be of copper where the phase conductors are of other approved material.
(3) All conductors and wires connecting the common neutral line conductor to ground shall be of copper.
B.
Size
The minimum sizes of wire of
various materials which shall be used for the several classes of construction
and loadings are listed in Table No. 7. These minimum sizes shall obtain in both
urban and rural districts. Larger sizes
of wire than those shown in the table will often be necessary to maintain
reasonable sag and at the same time provide the required safety factors of Rule 44, ground clearances of Table 1,
and wire clearances of Table 2.
In common primary and secondary
grounded neutral systems the common neutral line conductor shall have a minimum
area approximately not less than fifty (50) per cent of the area in circular
mills of the largest related primary phase conductor, and in no case shall have
less conductivity or mechanical strength than No. 6 A. W. G. copper.
In common primary and secondary
grounded neutral systems the size of the common neutral line conductor to be
used with related phase conductors shall be not less than those set forth in the
following table:
TABLE No. 6-A Minimum Sizes of Common Neutral Line Conductors |
|
Size of phase conductor |
Minimum size of neutral conductor |
500,000 C.M. |
4/0 |
350,000 C.M. |
3/0 |
250,000 C.M. |
2/0 |
4/0 |
1/0 |
3/0 |
1 |
2/0 |
2 |
1/0 |
3 |
1 |
4 |
2 |
6 |
4 |
6 |
6 |
6 |
This table is based upon the requirement that the common neutral line conductor shall have a minimum area of approximately fifty (50) per cent of the area of the largest related phase-conductor and that the phase and neutral conductors are of the same material. Where these are not of same material, the copper equivalents of the table shall be considered as meeting the requirements.
The minimum sizes of wire given in Table No. 7 are based upon spans not in excess of one hundred fifty (150) feet. Longer spans, except when specifically designated, may be employed without increasing the size of wire, provided the sags and conductor separations are so increased that the allowable working tensions and conductor clearances specified in this order are not violated.
Table 7 Minimum Allowable Conductor Sizes (150ft. span) |
||||||
Loading and Construction grade |
Material or Type of Conductor |
|||||
Soft drawn copper |
Hard-drawn copper |
Standard Aluminum wire |
Reinforced stranded Aluminum |
Copper-covered steel or |
Galvanized iron or steel wire |
|
A.W.G |
A.W.G |
A.W.G |
A.W.G |
A.W.G |
|
|
Heavy Loading, Grade “A” |
No. 4 |
No. 6 |
No. 1 |
No. 4 |
No. 6 |
¼ in diam. strand |
Heavy Loading, Grade “B” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Heavy Loading, Grade “C” |
4 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “A” |
4 |
6 |
1 |
4 |
8 |
*¼ in diam. strand |
Light Loading, Grade “B” |
6 |
6 |
1 |
6 |
8 |
No. 9 Steel W.G. |
Light Loading, Grade “C” |
6 |
8 |
1 |
6 |
40 |
No. 9 Steel W.G. |
Other supply service drops |
10 |
10 |
------- |
------- |
12 |
------- |
Supply service drops crossing trolley wires |
8 |
10 |
------- |
------- |
12 |
------- |
All Loadings Grade “F” |
------- |
12 |
------- |
------- |
12 |
No. 14 Steel W.G. |
All loadings of communication service drops, paired wires or bronze conductors |
------- |
14 |
------- |
------- |
17 |
------- |
* Three-sixteenth-inch strand may be used upon special permission of the Railroad Commission
C. Strength
(1) Heavy Loading Districts: Conductors in Grade “A” construction and in spans exceeding 150 feet shall have a tensile strength not less than that of No. 4 A.W.G hard-drawn copper, and said conductors shall preferably be stranded.
(2)
Light Loading Districts: The
following requirements apply for various grades of construction and span
lengths.
Conductors of Grade “A”
construction in spans not exceeding 300 feet in length shall have a tensile
strength not less than No. 6 A.W.G. hard drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 6 A.W.G. soft drawn copper.
Conductors of Grade “B” or “C”
construction in spans not exceeding 150 feet in length shall have a tensile
strength not less than No. 8 A.W.G. soft drawn copper, provided the voltage is
less than 750.
(3) Heavy or Light Loading Districts: Where signal or communication lines take Grade “B” or “C” classification other than at railroad crossings, a minimum size of No. 8 AWG hard-drawn copper or its equivalent in tensile strength may be used. In crossing over supply cables where Grade “C” construction is required No. 10 A.W.G. hard drawn copper or its equivalent may be used in spans not exceeding 150 feet.
(4) Conductors of Voltage Exceeding 17,000 Volts: Conductors of voltages exceeding 17,000 volts crossing conductors of less than 17,000 volts, crossing a public highway shall have a strength at least equal to No. 4 A.W.G. stranded hard-drawn copper. In lieu of this conductors carrying more than 17,000 volts shall, at the point of crossing, be supported on poles of such height and so placed that under no circumstance can the conductor of over 17,000 volts, or fall within a distance of ten feet from the surface of any public highway.
(5) Sags and Tensions: Conductor sags shall be such that under the assumed loading conditions the tension in the conductors shall not be more than one-half the breaking strength of the conductor, other than communication circuits. The minimum allowable sags for conductors calculated on this basis are given in Appendix C. The use of sags greater than allowable minimum may be desirable in order to reduce working tensions. Where sags greater than those indicated are used adequate clearance shall be provided. (See Rule 47.) Where the minimum size pins are used the conductor tensions shall be limited to 2000 pounds when applying the double arm, pin and conductor fastening provisions of Rules 49.2 and 49.3.
(6) Splices: Splices in line conductors shall be of equal or greater strength than the conductors in which they are made.
(7) Service Drops
a) Supply: The minimum sizes shall apply only where the span does not exceed 150 feet. The minimum for supply lines of like voltage and grade shall apply when the service drop is in excess of 150 feet. Supply service drops of 0-750 volts shall, in all cases, have an insulating covering equivalent to standard double braid weatherproofing.
b) Communication: Communication service drops of No. 16 AWG paired copper wire may be used provided they do not cross over supply lines, trolley contact or feeder conductors or railways.
D. Replacements (see Rule 44.2)
E.
Connections.
All electrical connections shall be soldered or of such rigid mechanical design
that there will be no material increase in the ohmic resistance of the circuit.