General Order 64
Section VI
Detail Construction Requirements For Supply Lines
64 Insulators.
(a) Insulators
used on supply lines shall be porcelain, glass or other equally suitable
material.
The insulators shall be so
designed that their dry flash-over voltage will be less than their puncture
voltage, at 60 cycles frequency. Strain
insulators shall be capable of withstanding under their mechanical loading at
least as high a voltage as line insulators in general.
(b) Insulators shall be capable of withstanding without flash-over at a frequency of 60 cycles, the voltages given in the following table:
Table 6 Insulator Minimum Flash-Over Voltages |
||
Voltages of circuit |
Flash-over voltage |
|
Dry |
Wet – 1-5 inch rain per minute – 45° |
|
750 |
5,000 |
3,500 |
2,300 |
11,000 |
8,000 |
4,000 |
17,000 |
13,000 |
6,600 |
27,000 |
17,000 |
7,500 |
30,000 |
18,000 |
11,000 |
40,000 |
20,000 |
15,000 |
55,000 |
25,000 |
22,000 |
75,000 |
40,000 |
33,000 |
105,000 |
65,000 |
44,000 |
125,000 |
85,000 |
55,000 |
150,000 |
100,000 |
66,000 |
170,000 |
115,000 |
88,000 |
225,000 |
165,000 |
110,000 |
275,000 |
200,000 |
150,000 |
350,000 |
250,000 |
200,000 |
450,000 |
300,000 |
For intermediate voltages use the value for flash-over voltages obtained by interpolation.
(c) All insulators or insulator units, used on lines on which the voltage exceeds 17,000, shall be subjected to flash-over test at frequency of 60 cycles, or to such other tests as may be generally sanctioned by good modern practice.
(d) Insulators used in territories where fog conditions prevail should be given more liberal factors of safety than those specified in the above table.
(e) Insulators, supports, clamps and miscellaneous attachments shall be designed to withstand with the designated factors shall be designed to withstand with the designated factors of safety, the tension in conductors, wires or structures under the loading conditions as specified herein.