Change List for this Rule

 

General Order 95

 

Section V

 

Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)

 

Figure 54-1
Figure 54-1

Minimum Vertical and Radial Clearances over Swimming Pools

A

Minimum

Vertical

B
Minimum
Radial

Unprotected Line Conductors (Vertical Over Highest Water Level and Radial from Top Edge of Pool Walls)
    1.    0 - 750 Volts
    2.    750 - 22,500 Volts
    3.    22.5 - 300 kV


20 Feet
25 Feet
30 Feet


20 Feet
25 Feet
30 Feet

Service Drops (Vertical Over Highest Water Level and Radial from Top Edge of Pool Walls
    4.    Pools Public and Commercial
    5.    Pools Residential
Service Drops (Over Diving Boards or Platforms)
    6.    Portion of Board or Platform That is Over Water Surface
    7.    Portion of Board or Platform That is not Over Water Surface


16 Feet
12 Feet

16 Feet
12 Feet


16 Feet
12 Feet

8 Feet
3 Feet

Guys (Ungrounded Portions)
    8.    Over Highest Water Level and from Top Edge of Pool Walls
    9.    Over Diving Board or Platform (The Portion that is Over the Water Surface)
    10.    Over Diving Board or Platform (The Portion that is not Over the Water Surface)


18 Feet
18 Feet
12 Feet


18 Feet
8 Feet
6 Feet

Guys (Grounded Portions)
    11.    Over the Highest Water Level
    12.    Over Diving Board or Platform (The Portion that is Over the Water Surface)
    13.    Over Diving Board or Platform (The Portion that is not Over the Water Surface)


16 Feet
16 Feet
8 Feet



8 Feet
3 Feet