General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
54.4 Clearances
Allowable variations in clearances due to side swing of suspension
insulators, temperature, loading, etc., are given in Rules
37
and 38.
A. Above Ground
The minimum vertical clearances shall be those specified
in Rule 37
, Table 1
, with the following modifications:
(1) Across Arid or Mountainous Areas: Across arid or mountainous areas
supply circuits carrying 22,500 - 30,000 volts, inclusive, may have a clearance
of less than 30 feet (Table
1, Case 4, Column F
) but not less than 25 feet above ground subject to a reduction of not
more than 10 percent because of temperature and loading as specified in
Rule 43
. Upon special permission from this Commission, a minimum clearance of
25 feet above ground may be applied in similar areas to circuits in excess
of 30,000 volts, however, not including Class E circuits. For circuits in
excess of 30,000 volts, no reduction of the 25 feet will be permitted for
conditions less than maximum loadings or temperature specified in Rules
43.1
and 43.2
.
Note: Revised March 29, 1966 by
Decision No. 70489; August 9, 1966 by Decision No. 71094; and March 30,
1968 by Decision No. 73813.
(2)
Lead Wires
for Transformers: Transformer lead wires shall have clearances above
ground as specified in Table 1
except as modified by the provisions of
Rule 58.1–B
.
Note: Revised January 21, 1992,
by Resolution SU–10.
(3) Over Swimming Pools: (See
Figure 54–1
) Installations of conductors, s
ervice drops and guys over swimming pools shall be avoided where practicable.
Where line conductors, service drop conductors or guys are installed over
swimming pools the following rules apply:
a) Line Conductors: Where unpr otected line conductors are installed over a swimming pool they shall have radial clearances from the top edge of the swimming pool walls and vertical clearances above the highest water level of the pool surface not less than the following:
1) 0 - 750 Volts - - 20 feet
2) 750 - 22,500 Volts - - 25 feet
3) 22.5 - 300 kV - - 30 feet
(See Table 1, Case 3, Columns
D, E and F
)
b) Service Drops 0 -
750 Volts: Where service drop con
ductors are installed over a swimming pool:
1) Phase conductors shall be suitably insulated (see Rule 20.9–G ).
2) Vertical clearances above the highest water level of the pool surface and radial clearances from the top edge of the pool wall shall be:
a) 16 feet for public and commercially operated pools.
b) 12 feet for residential pools.
3) No service drop may be installed less than 16 feet vertically above the horizontal plane through a diving board or platform, such plane being the area within 8 feet radially of the diving board or platform that is over the water surface of the pool.
4) No service drop may be installed less than 12 feet vertically above the horizontal plane through a diving board or platform, such plane being the area within 3 feet radially of the diving board or platform that is not over the water surface of the pool.
c) Ungrounded Portions of Guys:
1) Shall have radial clearances from the top edge of the swimming pool wall of not less than 18 feet.
2) Shall have vertical clearances above the highest water level of the pool surface of not less than 18 feet.
3)
Shall not be installed less than 18 feet vertically
above the horizontal plane through a diving board or platform, such plane
being the area within 8 feet radially of the diving board or platform that
is over the water surface of the pool.
4)
Shall not be installed less than 12 feet vertically above the
horizontal plane through a diving board or platform, such plane being the
area within 6 feet radially of the diving board or platform that is not
over the water surface of the pool.
d) Grounded Portions of Guys:
1)
Shall have vertical clearances above the highest water level
of the pool surface of not less than 16 feet.
2)
Shall not be installed less than 16 feet vertically above the
horizontal plane through a diving board or platform, such plane being the
area within 8 feet radially of the diving board or platform that is over
the water surface of the pool.
3)
Shall not be installed less than 8 feet vertically above the
horizontal plane through a diving board or platform, such plane being the
area within 3 feet radially of the diving board or platform that is not
over the water surface of the pool.
Note: Added January 2,
1962 by Resolution E–1109 and revised November 21, 1990 by Resolution No.
SU–6.
B. Above Railways and Trolley Lines
(1) Which Transport Freight Cars: The clearances specified in
Table 1, Case 1
, are based upon a maximum height of standard freight cars of 15 feet
6 inches from top of rail to top of running board. The clearance specified
in Table 1, Case 1, Column
C
shall not be reduced because of temperature or loading. The clearance
specified in Table 1, Case 1,
Columns A, B, D, E and F
, shall not be reduced more than 5% because of temperature or loading.
Note: Revised February 1, 1948 by Supplement No. 1, Decision No. 41134, Case
No. 4324.
(2) Operated by Overhead Trolley: The clearances specified in
Table, 1, Case 2, Columns D, E, and F
are based upon a trolley pole throw of 26 feet, the usual maximum height
of a free trolley pole above the top of rails or surface of streets used
by trolley cars or coaches. Above trolley lines having a maximum trolley pole
throw at variance of 26 feet, the specified clearances shall be increased
or may be reduced accordingly provided that the clearances specified in
Column F
shall not be reduced to less than 30 feet and the clearances specified
in
Columns D and E
shall not be reduced to less than 25 feet. See Rule 57.4–B2 for the clearances
required for grounded cables and messengers.
Where railways operated by overhead trolley transport freight cars,
the clearance requirements of Rule 54.4–B1
also apply.
C. Between Conductors
The minimum allowable clearances between conductors are specified in
Rule
38
, Table 2
, with the following modifications for supply conductors. (These modifications,
like the tabular values, are also subject to the allowable variations specified
in Rule 38
):
(1) On Different Crossarms on the Same Pole:
a) Conductors of 750 - 7,500 volts: The 4 foot vertical
clearance between conductors of 750 - 7,500 volts, as specified in
Table 2, Case 10, Column E, may be reduced to not less than 2 feet provided all the following conditions
are met:
The conductors involved are of one ownership and the circuits are operated and maintained by the same crews of workmen;
Under no conditions is this reduced clearance to be applied in new construction involving new poles;
Buck arm construction, transformers or capacitors are not involved;
More than one reduced clearance of 2 feet shall not be used on any pole; and
It is not practicable to obtain the normally required 4 foot clearance.
b) Conductors of 7,500 - 20,000 volts: The 4 foot vertical clearance
between conductors of 7,500 - 20,000 volts, as specified in
Table 2, Case 11, Column F
, may be reduced to not less than 3 feet, provided all of the following
conditions are met:
The conductors involved are of one ownership and the circuits are operated
and maintained by the same crews of workmen;
Under no condition is this reduced clearance to be applied in new construction
involving new poles;
Buck arm construction, transformers or capacitors are not involved;
More than one reduced clearance of 3 feet shall not be used on any pole;
and
It is not practicable to obtain the normally required 4 foot clearance.
c) Triangular and Vertical Configuration on Different Crossarms on
the Same Pole: When crossarms are used to support conductors of the
same circuit at different levels (as in triangular or vertical configuration),
the crossarms may be arranged so that the vertical separation of the conductors
of the same circuit shall not be less than the pin spacings of
Table 2, Case 15.
Where circuits are installed on crossarms in vertical or triangular
configuration with vertical conductor separations less than as specified
in Table 2, Cases 9 to 13
, not more than two circuits shall be installed on the same crossarms
and the conductors of both circuits shall be arranged in identical physical
configuration on opposite sides of the pole except at points of transposition.
When different voltage classifications are involved, the vertical separation
of the conductors shall not be less than the pin spacing for the higher
voltage.
For pole–top triangular construction with crossarms involving a single
circuit see Rule 54.4–D8.
For pole–top triangular and vertical construction without the use of
wood crossarms see Rule 54.11
.
Note: Revised
May 22, 1990 by Resolution No. SU–5.
(2) On Related Line and Buck Arms:
a) One voltage Classification*: The clearances of
Table 2, Case 14
(and clearances less than as specified in
Cases 9 to 13
) shall not be applied consecutively both above and below the same conductor.
The foregoing provisions of this rule do not apply to conductors in triangular
or vertical configuration, the clearances of
Table 2, Case 14
being directly applicable.
Where conductors of one voltage classification only are supported on
the same crossarms, the vertical clearances specified in
Table 2, Case 14
, are not required between conductors on line arm and conductors on related
buck arm provided no conductors on the line arm cross conductors of different
phase or polarity on the buck arm.
*Voltage classifications for this purpose are:
0 - 750 Volts |
750 - 7,500 Volts |
7,500 - 20,000 Volts |
20,000 - 75,000 Volts |
Note: Revised March 30, 1968 by Decision No. 73813.
b) Combination Arms: Where conductors of 0 - 750 volts and conductors
of 750 - 7,500 volts are supported on the same crossarms with the nearest
conductors of the two classifications separated a horizontal distance of
not less than 36 inches (plus any necessary vacant pin spaces required by
Rule 54.7–A3c
) the vertical separation between conductors on such a line arm and conductors
on a related buck arm shall be not less than 4 feet. This vertical separation
may be less than 4 feet but not less than 2 feet provided the horizontal
separation of conductors of the two classifications is not less than 42 inches
(plus any necessary vacant pin spaces required by
Rule 54.7–A3c
) and all conductors of the same voltage classification are supported on
the same ends of the crossarms.
Where this vertical separation of 2 feet (or less than 4 feet but more
than 2 feet) between conductors on a line arm and related buck arm is utilized,
any conductor on such line or buckarm shall have a vertical clearance from
any other conductor level of not less than clearances specified in
Table 2, Cases 8 to 13
.
(3)
On the Same Crossarms:
a) Different Voltage Classifications: Supply conductors of different
voltage classifications may be supported on the same crossarms in conformity
with the requirements of Rule 32.4
.
b) On Brackets Attached to Crossarms: Line conductors supported
on brackets or extensions attached to crossarms shall be maintained outside
of the outer pin position on the crossarm with a radial separation not less
than the minimum pin spacing specified in
Table 2, Case 15
, from any other line conductors supported by the same arm. Line conductors
supported on such brackets or crossarm extensions shall be of the same voltage
classification as the conductors supported on the same side of pole by
the crossarm to which the bracket or arm extension is attached. The vertical
clearances specified in Table 2, Cases 1 to
14
shall be provided between the conductor on the bracket and the conductor
level of any other conductors not supported on the crossarm to which the
bracket is attached.
c) Same Phase or Polarity: The clearances specified in
Table 2, Cases 15 and 17
, are not required between conductors of both the same potential and
the same phase or polarity.
(4) Deadended on Pole in Vertical Configuration:
a) Conductors of 750 Volts or Less: Where conductors of 750 volts
or less are supported in vertical configuration directly on a pole without
the use of crossarms, the requirements for rack construction,
Rule 54.9
, shall apply.
b) Conductors of More than 750 Volts Supported on Climbable Poles:
Where conductors of more than 750 volts are supported in vertical configuration
directly on a climbable pole without the use of crossarms at line terminations,
angles or corners, the following requirements apply:
The vertical separation between conductors of the same circuit shall
not be less than the clearances specified in
Table 2, Cases 15 and 20;
The vertical separation of different circuits shall not be less than
the clearances specified in
Table 2, Cases 8 to 13
, inclusive;
Not more than four conductors of a circuit of more than 750 volts shall
be supported directly on a pole in vertical configuration without the use
of crossarms. Branch circuits may be taken from such construction without
the use of crossarms provided a climbing and working space as specified
in Rule 54.7
and 54.11
is maintained; and
The clearance of conductors from surface of pole shall not be less than
as specified in Rule 54.4–D6b
.
See Rule 54.11–F
for climbing space requirements for conductors dead ended on poles in
vertical configuration.
Note:
Revised February 7, 1964 by Decision No. 66707; January 6, 1968 by Decision
No. 73455; and January 21, 1992, by Resolution SU–10.
c) Conductors of More than 750 Volts Supported on Nonclimbable Poles:
Where conductors of more than 750 volts are supported in vertical configuration
on nonclimbable poles in partial underground distribution at line terminations,
angles, or corners, the following requirements apply:
Not more than four conductors of a single circuit of 750 - 22,500 volts
shall be supported directly on the pole in vertical configuration without
the use of crossarms. Branch circuits may be taken from such construction
without the use of crossarms provided that conductors are supported on
not more than three sides of the pole, there being four sides;
The vertical separation between conductors shall not be less than the
pin spacings specified in
Table 2, Case 15
; and
The clearance of conductors from surface of pole shall not be less than
as specified in Rule 54.4–D2
.
Note: Added February 7, 1964 by Decision No. 66707; Amended March 29, 1966 by Decision No.70489; Revised August 9, 1966 by Decision No. 71094 and November 21, 1990 by Resolution No. SU–6.
(5) Rack Construction (See Rule 54.9
)
Extended Rack Construction (See Rule
54.12
)
Note: Revised January 21, 1992 by Resolution SU–10.
(6) From Lead Wires and Drip Loops to Other Conductors:
The vertical clearances between the lowest point of lead wires (to conduit
runs, transformers or other equipment), excepting drop wires to street lights,
and the next supply conductor level below such lead wires may be less than
the clearances specified in
Table 2, Cases 9 to 12, Columns D, E, F and G,
provided the vertical separation is maintained as great as practicable
and in no case less than the following (see
Figure 54–22
):
Voltage of Lead Wires |
Minimum Distance above Other Conductor Level |
0 - 750 |
12 inches |
750 - 7,500 |
18 inches |
7,500 - 20,000 |
24 inches |
20,000 - 35,000 |
36 inches |
(7) Vertically at Crossings in Spans:
The Vertical clearance required at crossings in spans by
Table 2, Cases 4, 5, 6 and 7
, may be reduced when:
1) All conductors are of the same circuit, and
2) Vertical taps are installed between related crossing conductors.
The minimum vertical clearance shall be the following:
Supply Conductor Voltage: |
Minimum VerticalClearance: |
0 - 750 Volts |
12 inches |
750 - 20,000 Volts |
24 inches |
20,000 - 35,000 Volts |
30 inches |
35,000 - 75,000 Volts |
48 inches |
EXCEPTIONS:
a) In vertical configuration, there is no specific vertical clearance
required between conductors that are mechanically and electrically connected
at the crossing.
b)
There is no specific clearance required for 0 - 750 volt multiconductor
cable having a bare neutral (Rule 54.10
) provided the messengers are mechanically connected.
Note: Rule 54.4–C7 deleted March 30, 1967 by Decision
No. 73813. Added again on November 6, 1992 by Resolution SU–15.
D. From Poles
The basic minimum clearances of conductors from centerline and surface
of poles are specified in
Table 1, Cases 8 and 9.
Modifications of these basic clearances are specified in
Rule 37
and by the following provisions:
(1) Center Line Clearance at Angles in Lines: The clearance specified
in Table 1, Case 8
may be reduced at angles in lines where it is necessary to support conductors
on the side of insulators placed on pole–pins, provided the distance between
the center of any such pole–pin and the centerline of the crossarm through
bolt is not less than the distance specified in
Table 1, Case 8
. This Rule 54.4–D1
shall not be held to permit any greater reduction of climbing space
widths than that specified in Rule 54.7–A
for line angles.
Note:
Revised May 22, 1990, by Resolution SU–5.
(2) Center Line Clearances for 750 Volts and above: The clearances referred to in Table 1, Case 8, Columns E and F , apply as follows with respect to voltage:
750 - 7,500 Volts |
15 inches |
7,500 - 46,000 Volts |
18 inches |
46,000 Volts and above |
18 inches plus 1/4 inch per kV in excess of 46 kV |
These clearances from centerline of pole need not apply to conductors
of 750 - 7,500 volts and 7,500 - 22,500 volts supported in vertical configuration
in partial underground distribution provided: a) such conductors have clearances
from surface of pole of not less than 6 inches, b) in tangent construction,
conductors so supported are not attached to more than one side of pole,
and c) in deadend construction conductors so supported are not attached to
more than three sides of a pole (there being four sides, see
Figure 54-3
).
Note:
Revised February 7, 1964
by Decision No. 66707; March 29, 1966 by Decision No. 70489 and August 9,
1966 by Decision No. 71094.
(3) Conductors Passing and Unattached: The centerline clearance
between poles and conductors which pass unattached shall be not less than
1–1/2 times the clearance specified in
Table 1, Case 8
, except where the interset pole is within 10 feet of a pole to which
the passing conductors are attached or where the provisions of
Table 1, Case 10, Columns D, E, F, and G
can be applied. Where poles of the two lines are less than 10 feet apart,
clearances not less than as specified in
Table 1, Case 8
, shall be maintained between the center line of any pole and conductors
which pass unattached.
Note:
Revised January 8, 1980
by Decision No. 91186.
This rule will often necessitate the use of clearance crossarms with
conductor clearances as specified in
Table 1, Case 8
, or the alternate increased clearances for service drops as provided
in
Rule 54.8–C3
.
(4) Longitudinal Cables and Messengers: Messengers and longitudinal
supply cables, treated as required in
Rule 57.4–F
, may be attached to the surface of pole and thus have clearances less
than as specified in Table 1,
Cases 8 and 9, Column D.
(5) Rack Construction for 0 - 750 Volts: Conductors of 0 - 750 volts
in rack construction may be attached to poles with clearances less than
15 inches and 3 inches as specified in
Table 1, Cases 8 and 9
respectively, provided such construction complies with the provisions
of Rule 54.9
and such conductors, not including their tie wires, shall have a clearance
of not less than 2 1/2 inches from surface of pole.
(6) Deadended on Pole:
a) 0 - 750 Volts: Where conductors of 0 - 750 volts are dead ended
on a pole in vertical configuration, the clearances specified for rack
construction, Rule 54.9–B1
, shall apply.
b) More than 750 Volts Supported on Climbable Poles: Where conductors
are supported on a climbable pole in vertical configuration, the energized
portions of such conductors shall have clearances of not less than 15 inches
from the surface of the pole for voltages between 750 and 7,500 volts and
18 inches from the surface of pole for voltages in excess of 7,500 volts.
Not more than four conductors of a circuit of more than 750 volts shall
be attached directly to a pole in vertical configuration without the use
of crossarms. Branch circuits may be taken from such construction without
the use of crossarms provided a climbing and working space as specified
in Rules
54.7
and 54.11
is maintained.
Note:
Revised February 7, 1964 by Decision No. 66707; January 6, 1968 by Decision
No. 73455; July 22, 1968 by Decision No. 74342;and January 21, 1992, by
Resolution SU–10.
c) More than 750 Volts Supported on Nonclimbable Poles: Where conductors
are deadended on a nonclimbable pole in partial underground distribution,
the energized portions of such conductors shall be not less than 6 inches
from surface of pole (see Rule 54.4–D2
).
Note:
Added February 7, 1964 by Decision No. 66707.
(7) This space is intentionally left blank.
(8) At Top of Pole:
Clearance between a Single Conductor and Center Line of Pole: A single
conductor of a circuit may be attached directly to the top of a pole or
to a crossarm at the top of a pole at a distance less than as specified in
Table 1, Case 8
. Where a transformer(s) or similar apparatus is connected to a circuit
so arranged, a vertical clearance of not less than 30 inches shall be maintained
between its unenergized metal parts and the lowest primary line conductor
of the circuit directly above.
For pole–top triangular and vertical construction without the use of
wood crossarms see Rule 54.11
.
Note:
Revised March 29, 1966 by Decision No. 70489;
August 9, 1966 by Decision No. 71094;March 9, 1988 by Resolution E–3076,
May 22, 1990 by Resolution SU–5 and October 9, 1996 by Resolution SU–40.
(9) Lateral and Vertical Conductors: Unprotected lateral and vertical
conductors (excepting ground wires installed as specified in
Rule 54.6–B
, bond wires installed as specified in
Rule 53.4
, and suitable insulated conductors of 0 - 750 volts entering terminal
fittings mounted on the surface of poles as specified in
Rule 54.6–F
) shall not be attached to the surface of poles, but shall be supported
on crossarms or other supports and arranged to maintain the specified clearances
from poles, towers or structures and other conductors (
Table 1, Cases 8 and 9, and Table 2, Cases 15, 16 and 17
), and to maintain the climbing and working spaces as required in
Rule 54.7
. In lieu of the foregoing, lateral and vertical conductors may be installed
on the surface of poles provided the conductors are suitably insulated and
protected as specified in Rule 54.6
.
E. From Crossarms
The minimum distances of unprotected conductors from the surface of
crossarms are specified in
Table 1, Case 9.
These clearances from the surface of crossarms are not required for
suitably insulated conductors in runs which are protected as specified
in Rule 54.6–C
or for suitably insulated conductors where entering such protected runs.
Lead wires of 0 - 5,000 volts may be less than 3 inches, but shall be
not less than 1 inch, from the surface of crossarms where equipment (cutouts,
switches, etc.) mounted on the crossarms is so constructed that clearances
of less than 3 inches are necessary for the entrance of such leads to the
equipment.
F. From Guys and Messengers (See
Table 2, Column A
, Rule 56.4–C
and Rule 57.4
)
G. From Grounded Metal Boxes, Hardware and Equipment
All grounded metal boxes, hardware and grounded metal cases for equipment,
on non–metallic poles or non–metallic structures shall be a minimum of 36
inches above and 30 inches below the next level of unprotected conductors.
Such equipment shall have a minimum clearance of 48 inches above or 72 inches
below communication line conductors, cables and messengers of different
ownership. See
Figure 54–4
.
EXCEPTIONS:
(1) 0 - 750 volt line conductors (not including incidental pole
wiring, e.g. jumpers) a 10 inch radial clearance is required.
(2) Equipment (e.g. in Rule 58.6) operated at 0 - 750 volts and
mounted not less than 15 inches from the surface of the pole. These clearances
shall not be less than the radial clearances required for incidental pole
wiring by Table 2, Cases 16
and 17
.
(3) Grounded portions of risers and their associated terminal fittings,
brackets and hardware. These clearances shall not be less than the radial
clearances required for incidental pole wiring by
Table 2, Cases 16 and 17
.
(4) Lightning arresters, grounded insulator pins and insulators
with grounded bases and their associated supports. These clearances shall
not be less than the radial clearances required for incidental pole wiring
by
Table 2, Cases 16 and 17
.
(5)
The 72 inches may be reduced to not less than 48 inches where
a communication cable does not have a pole mounted drop distribution terminal
located above the grounded metal box, hardware or metal case for equipment,
or where the grounded metal box, hardware or metal case for equipment is
securely bonded to the communication cable and/or messenger.
(6)
The 72 inches may also be reduced to 48 inches when the grounded
metal box, hardware or metal case for equipment is on the opposite side
of a pole from a pole mounted communication drop distribution terminal.
Any item grounded in accordance with this rule shall be effectively
grounded (see Rule 33.3
).
Note: Revised
January 19, 1994 by Resolution SU–25 and October 9, 1996 by Resolution
SU–40.
H. Above, alongside, or in Immediate Proximity to
Buildings, Bridges and Other Structures
(1) Unattached Conductors: Conductors should be arranged so as not
to hamper or endanger workers and firefighters while performing their duties.
The basic clearances of conductors from buildings are specified in
Table 1, Cases 6 and 7
. The horizontal clearance (
Table 1, Case 7
) shall be maintained until the vertical clearance (
Table 1, Case 6
) is attained (see
Figure 54–24
). The requirements of Table
1, Case 7
, also apply at fire escapes, exits, windows, etc., at which human contact
may be reasonably expected.
EXCEPTION: The horizontal conductor clearance from buildings may
be reduced from 6 feet to 4 feet (
Table 1, Case 7, Column E
) if all of the following criteria are met:
a) The conductor voltage is 7,500 volts or less; and
b) The conductor vertical clearance above ground is more than 35
feet; and
c) The building height next to the conductors exceeds the conductor height by 6 feet or more; and
d) There are no fire escapes, exits, or windows at which human contact
may be reasonably expected.
Note: See Rule 54.8–B4
for service drop clearance requirements and
Table 58–1
for special treatment of bus and lead wires of transformer installations
in alleys.
(2) Attached Conductors: Unprotected conductors not exceeding 22,500
volts may be supported by attachments to buildings, bridges and other structures.
To conductors of 0 - 750 volts so supported, the clearances of
Table 1, Case 7, Columns B, C and D
shall apply. To conductors of 750 - 22,500 volts so supported a minimum
horizontal clearance of 8 feet shall apply.
In lieu of these requirements for unprotected conductors, supply conductors
may be installed on the surface of buildings, bridges and other structures
in grounded metal conduit or other grounded sheath or grounded shield suitably
protected from mechanical injury.
Note: Revised March 29, 1966 by Decision No. 70489; August
9, 1966 by Decision No. 71094; November 6, 1992 by Resolution SU–15 and
January 19,1994 by Resolution SU–25.
I. Below, alongside, through or in Immediate Proximity
to Bridges, Viaducts or Similar Structures
Unprotected supply conductors which pass unattached below or in immediate
proximity to bridges, viaducts or similar structures shall be maintained
at clearances above ground and walkways as specified in
Table 1, Cases 1 to 6
inclusive; at clearances from walls and underneath parts of such structures
as specified in Table 1, Case
7
; and at clearances from conductors of other classifications as specified
in Table 2, Case 3
. The horizontal clearance (
Table 1, Case 7
) shall be maintained until the vertical clearance (
Table 1, Case 6
) is attained (see
Figure 54–24
).
Conductors of 0 - 22,500 volts, passing under or through bridges, viaducts
or similar structures may be attached thereto in accordance with the provisions
of Rule 54.4–H2
. Warning signs of a substantial character with letters not less than
3 inches in height reading “High Voltage” for voltages in excess of 750
volts shall be placed conspicuously on each crossarm or structural member
supporting the conductors.
In lieu of these requirements for unprotected conductors, supply conductors
which cross below bridges, viaducts or similar structures shall be enclosed
in grounded metal conduit or in other effectively grounded sheath or grounded
shield suitably protected from mechanical injury.
Note: Revised March 29, 1966 by Decision No. 70489 and August 9, 1966 by Decision No. 71094 and November 6, 1992 by Resolution SU–15.