General Order 95
Section III
Requirements for All Lines
32.2
Relative Levels
Where supply and communication circuits or supply circuits of
different voltage classifications are involved in crossings, conflicts or
joint use, the higher voltage circuit shall in general be carried at the
higher level. This arrangement is not feasible in all cases, for example where
trolley circuits are involved or where poles are jointly occupied.
It is recommended that lines be arranged by mutual agreement
of those concerned at standardized voltage levels throughout a given community
in order to minimize difficulties when new crossings or extensions to existing
lines are to be installed.
A. Supply Circuits of 750 - 20,000 Volts
Supply circuits of 750 - 20,000 volts should not be above
supply circuits in excess of 20,000 volts.
D. Communication Circuits
Communication circuits should not be
above supply circuits in excess of 7,500 volts. Insulated single conductors,
paired wire or duplex communication line conductors above supply circuits
(including Class T circuits) of 750 - 7,500 volts shall be supported on messengers
or constructed in accordance with Rule
32.2–G
.
E. Supply Service
Drops of 0 - 750 Volts
Supply service drops of 0 - 750
volts shall not cross in a span above supply circuits (excepting Class T
circuits) in excess of 750 volts, but service drops may cross above such circuits
when supported on the same pole.
F. Communication
Service Drops
Communication service drops
should not cross in a span above supply circuits (excepting Class T circuits)
of 750 - 7,500 volts and shall not cross in a span above supply circuits
in excess of 7,500 volts. Where it is necessary that communication service
drops cross in a span above supply circuits of 750 - 7,500 volts, an auxiliary
attachment or its approved equivalent shall be used at the service end of
the service drop to insure against the drop falling across the supply circuit
in the event of the failure of the usual means of attachment.
G. Exceptional
Cases
Where it is not possible
to conform to the usual arrangement whereby the higher voltage circuit shall
be carried at the higher level, the positions may be reversed provided the
lower voltage circuit, installed at the higher level, shall be erected and
maintained with the same strength requirements as the higher voltage circuits
would require with the usual arrangement of levels. Where neither circuit
carries in excess of 750 volts this provision does not apply.
Where supply and communication
circuits carrying less than 750 volts cross trolley contact conductors carrying
in excess of 750 volts, they shall conform to the strength requirements for
supply lines corresponding to the voltage of the trolley contact conductors.