General Order 95
  
    
Section V
 
 Detailed Construction Requirements for Supply Lines
  (Class H, L and T Circuits)
  
56.6    Requirements for Sectionalizing With Insulators
   
A.    Guys in Proximity to Supply Conductors of Less than 
35,500 Volts (See Rule 21.5–D
 for definition of “proximity” and 
 Figure 56–3
  )
        
    
All portions of guys within both a vertical distance of 8
 feet from the level of supply conductors of less than 35,500 volts and a
radial distance of 6 feet from the surface of wood poles or structures shall
not be grounded, through anchors or otherwise. Where necessary to avoid the
grounding of such portions, guys shall be sectionalized by means of insulators
installed at locations as specified in Rule
56.7
.
        
        
Note:    Revised March 29, 1966 by Decision 
No. 70489; August 9, 1966 by Decision No. 71094; November 20, 1979 by Decision
 No. 91030; and January 21, 1992, by Resolution SU–10.
               
      
 B.    Guys to Arms Supporting Conductors of Less than 35,500 
Volts
                    
    
All portions of arm guys within 6 feet of points of
 attachment to wood crossarms, or metal crossarms on wood poles, shall not
 be grounded if the crossarms support supply conductors of less than 35,500
 volts. Where necessary to avoid the grounding of such portions, arm guys
shall be sectionalized by means of insulators at locations as specified in
            Rule 56.7
.
              
        
Note:    Revised March 29, 1966 by Decision
 No. 70489; August 9, 1966 by Decision No. 71094 and November 20, 1979 by
Decision No. 91030.
                           
            
C.    Ungrounded Overhead Guys
              
                                
    
All overhead guys which are not grounded (by
means of ground wires, grounded anchor guys, attachment to grounded metal
poles, or otherwise) shall be sectionalized at the locations measured from
each attachment to poles or structures, as specified in 
Rule 56.7–A
 (6 feet to 9 feet from attachments).
                    
        
 D.    Guys Exposed to 22,500 Volts or More (See 
Rule 21.5–C
 for definition of “exposed” and 
  Figure 56–4
  )
                                            
    
Guys exposed to conductors of 22,500 volts
 or more shall not be sectionalized and shall be securely grounded (by means
 of ground wires, anchor guys, or attachments to securely grounded metal
poles  or structures). 
                          
        
        
EXCEPTED from the above requirements
 are:
                              
        
        
(1)    Guys, all or any portions thereof, which are required to be sectionalized 
in accordance with Rule 56.6–A
 because of proximity of wood poles and supply conductors of less than 22,500
volts or in accordance with Rule 56.6–B
; and
                                  
        
        
 (2)    Guys which are sectionalized by wood strain insulators equipped with 
arcing horns and designed to provide impulse insulation for lightning conditions 
or, glass fiber noninterlocking strain insulators which are designed to provide 
impulse insulation for lightning conditions.
                                      
        
Note:    Revised
 July 8, 1959 by Resolution No. E–1030; March 29, 1966 by Decision No. 70489;
 August 9, 1966 by Decision No. 71094; January 6, 1968 by Decision No. 73455;
 and January 21, 1992, by Resolution SU–10.
                                                                        
  
                                    
 E.    Guys Attached to Grounded Poles or Structures
                                                                                
    
Guys attached to securely
 grounded metal poles or structures are not required to be sectionalized
except  as required by Rule 56.6–A
 because of proximity to supply conductors of less  than 35,500 volts supported
on wood poles, or by Rule 56.6–B
.
                                            
        
Note: Revised March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094 and November 20, 1979 by Decision No. 91030.