General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
56.6 Requirements for Sectionalizing With Insulators
A. Guys in Proximity to Supply Conductors of Less than
35,500 Volts (See Rule 21.5–D
for definition of “proximity” and
Figure 56–3
)
All portions of guys within both a vertical distance of 8
feet from the level of supply conductors of less than 35,500 volts and a
radial distance of 6 feet from the surface of wood poles or structures shall
not be grounded, through anchors or otherwise. Where necessary to avoid the
grounding of such portions, guys shall be sectionalized by means of insulators
installed at locations as specified in Rule
56.7
.
Note: Revised March 29, 1966 by Decision
No. 70489; August 9, 1966 by Decision No. 71094; November 20, 1979 by Decision
No. 91030; and January 21, 1992, by Resolution SU–10.
B. Guys to Arms Supporting Conductors of Less than 35,500
Volts
All portions of arm guys within 6 feet of points of
attachment to wood crossarms, or metal crossarms on wood poles, shall not
be grounded if the crossarms support supply conductors of less than 35,500
volts. Where necessary to avoid the grounding of such portions, arm guys
shall be sectionalized by means of insulators at locations as specified in
Rule 56.7
.
Note: Revised March 29, 1966 by Decision
No. 70489; August 9, 1966 by Decision No. 71094 and November 20, 1979 by
Decision No. 91030.
C. Ungrounded Overhead Guys
All overhead guys which are not grounded (by
means of ground wires, grounded anchor guys, attachment to grounded metal
poles, or otherwise) shall be sectionalized at the locations measured from
each attachment to poles or structures, as specified in
Rule 56.7–A
(6 feet to 9 feet from attachments).
D. Guys Exposed to 22,500 Volts or More (See
Rule 21.5–C
for definition of “exposed” and
Figure 56–4
)
Guys exposed to conductors of 22,500 volts
or more shall not be sectionalized and shall be securely grounded (by means
of ground wires, anchor guys, or attachments to securely grounded metal
poles or structures).
EXCEPTED from the above requirements
are:
(1) Guys, all or any portions thereof, which are required to be sectionalized
in accordance with Rule 56.6–A
because of proximity of wood poles and supply conductors of less than 22,500
volts or in accordance with Rule 56.6–B
; and
(2) Guys which are sectionalized by wood strain insulators equipped with
arcing horns and designed to provide impulse insulation for lightning conditions
or, glass fiber noninterlocking strain insulators which are designed to provide
impulse insulation for lightning conditions.
Note: Revised
July 8, 1959 by Resolution No. E–1030; March 29, 1966 by Decision No. 70489;
August 9, 1966 by Decision No. 71094; January 6, 1968 by Decision No. 73455;
and January 21, 1992, by Resolution SU–10.
E. Guys Attached to Grounded Poles or Structures
Guys attached to securely
grounded metal poles or structures are not required to be sectionalized
except as required by Rule 56.6–A
because of proximity to supply conductors of less than 35,500 volts supported
on wood poles, or by Rule 56.6–B
.
Note: Revised March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094 and November 20, 1979 by Decision No. 91030.