General Order 95
  
    
Section V
 
 Detailed Construction Requirements for Supply Lines
  (Class H, L and T Circuits)
  
59.3    Conductors
   
A.    Material
   
        
    
Conductors of common neutral systems shall be of suitable
 corrosion–resisting materials, but shall not be of galvanized iron or steel.
        
        
Note:    Revised January 21, 1992, by Resolution
 SU–10; November 6, 1992 by Resolution SU–15.
               
      
B.    Size
         
                    
    
In common neutral systems, the neutral line conductor
 shall have a minimum ampacity at each location of not less than one–quarter
 (25%) that of the largest related primary phase line conductor, provided
that the short time ampacity of the neutral conductor is maintained. 
The short time ampacity of a common neutral conductor is either:  the
current that a non–insulated conductor can carry for the time which the current
flows without annealing, melting or separating under the applied tensions;
or the current that an insulated conductor can carry for the time that the
current flows without damaging the insulation.
              
        
        
No neutral line conductor need have greater ampacity
 than either:  the phase line conductor which would supply the ground
 current, or the maximum current which can flow through the neutral line
conductor  to the ground or electrode of the common neutral grid system. 
The neutral  line conductor shall have a short time ampacity adequate for
the fault current  which can flow in the neutral line conductor for the operating
time of the  system protective device.  If this value cannot be readily
determined,  the continuous ampacity of the neutral line conductor shall
not be less than  the full load continuous current of the system supply transformers
or other  source of supply.  In no case shall the neutral conductor
have less ampacity than No. 6 AWG medium–hard–drawn copper wire.
                  
        
Note:    Revised March 29, 1966 by
 Decision No. 70489; August 9, 1966 by Decision No. 71094; November 6, 1992
 by Resolution SU–15.
                                   
                
C.    Connections
                                        
    
All electrical connections shall be of suitable
 electrical and mechanical design.
                        
        
D.    Arrangement and
 Continuity
                         
                                                    
    
The arrangement and continuity of common
 neutral conductors shall conform to the following requirements:
                              
        
        
 (1)    Continuity: Cross ties of the common neutral conductor shall be
made to form a continuous interconnected grid network.
                                  
        
        
 (2)    Minimum Number of Return Paths: There shall not be less than two 
separate and continuous metallic return conductor paths from the grid network 
to the substation constituting the source of supply thereto.
                                      
        
        
 (3)    Two Return Conductor Paths: If only two return common neutral conductors 
paths are used, each path shall have a minimum ampacity of not less than one–quarter
(25%) that of the largest related primary phase conductor, provided that
the short time ampacity of the common neutral conductor is maintained.
                                          
        
        
 (4)    More Than Two Return Conductor Paths:  If more than two return 
common neutral conductors paths are used, the ampacity of the return system 
shall be such that a break in any one path shall leave two or more return 
common neutral paths.  These combined paths shall have a minimum ampacity 
of not less than one–quarter (25%) that of the largest primary phase conductor 
of the overhead feeder serving the area, provided that the short time ampacity 
of the common neutral conductor is maintained. 
                                              
        
        
 (5)    Primary and Secondary Neutral Conductors:  Primary neutral
conductors or secondary neutral conductors, where continuous, may be used
as a return loop from a common neutral provided they have sufficient ampacity
as specified  in Rule 59.3–B
 and are grounded throughout in accordance with the requirements  for common
neutral conductors as specified in Rule
59.4–B
.  Primary or secondary neutral line conductors so used shall be carried
in the normal primary or secondary positions, respectively.
                                                  
        
Note:    Revised March 29,1966 by Decision No. 70489; August 19, 1966 by Decision
 No. 71094; November 6, 1992 by Resolution SU–15.
                                                                        
                          
                                                
 E.    Common Neutral Line Conductor Location
                                                                                                        
    
 (1)    With Primary Circuits:  On poles where all circuits are in
excess of 750 volts, the common neutral line conductor may be located in
a conductor  position in the primary space.
                                                        
        
        
 (2)    With Secondary Circuits:  On poles where all circuits of a
common  neutral system are of less than 750 volts, the common neutral line
conductor  shall be located in a secondary conductor position.
                                                            
        
        
  (3)    With Primary and Secondary Circuits:  On poles where circuits
 of a common neutral system are of more and less than 750 volts, the common
 neutral line conductor shall be located in a related secondary conductor
position; or common neutral line conductors may be located in both primary
and secondary positions provided a metallic connection of a size not smaller
than the largest neutral line conductor involved is installed between the
neutral conductors in accordance with the construction requirements for ground
wires on poles at each location where a ground is required, and provided
proper designation (see Rule 59.3–F
) is made of the common neutral conductor in the primary position.
                                                                
        
        
  (4)    In Metal Riser Conduits:  Common neutral conductors may be 
installed in the same metal riser conduits with related phase conductors, 
provided that the metal riser conduit is effectively grounded. 
                                                                    
        
Note:    Revised November 6, 1992 by Resolution SU–15.
                                                                        
                                                              
                                                                  
  (5)    Under Crossarms:  Incidental pole wiring connected to the
common  neutral conductor may be stapled to the underside of crossarms, provided
the installation is such as to offer the least possibility of contact to
workmen and such wiring under crossarms, in the primary position, is covered
by a suitable protective covering.
                                                                        
        
F.    Designation of Common Neutral
                                                                        
                                                                        
                                                                        
                                                                        
                                                                                                                                                  
    
In common neutral systems, where the common neutral line conductor is installed
 in a primary pin position, it shall be designated at each pin position with
 the letters “CN”.  A weather and corrosion–resisting material shall
be used and the letters shall be clearly legible.
                                                                        
       
        
        
Optional marking methods are:
                                                                        
         
        
        
  (1)    A tag having a minimum diameter of not less than 1 inch upon 
which  shall be permanently imprinted the letters “CN” not less than 5/16
inch in  height. Said tag shall be attached securely to and maintained on
the common  neutral conductor at a distance not more than 12 inches from
the surface of the conductor support.
                                                                        
             
        
        
  (2)    Solid letters not less than 3 inches in height or a sign showing the
 letters “CN” not less than 3 inches in height, solid or with letters cut
out therefrom. Said letters or signs shall be placed on the face of a crossarm,
 suitable for attaching the letters or signs, directly beneath the common
neutral support, or said letters or signs shall be placed on the surface
of the pole beneath the common neutral support.