General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
59.4 Grounding
A. Material and Size
(1) Grounding Conductors: The grounding conductors of the common neutral
system shall conform to each of the following requirements:
a) The grounding conductor from each ground rod to the base of the pole
shall not be less than 1 foot below the surface of the ground.
b) The grounding conductor from each ground rod to the base of the pole
shall not have less ampacity and mechanical strength than the grounding conductor
from the base of the pole to the common neutral conductor.
c) The grounding conductor from the ground rod to the common neutral conductor
shall be continuous, unless suitable electrical compression connections are
used.
d) The grounding conductor shall have a minimum ampacity equivalent to
No. 4 AWG copper.
Note: Revised September
11, 1974 by Decision No. 83420; November 6, 1992 by Revision SU–15.
(2) Ground Rods (Ground Electrodes): Ground rods on common neutral
systems shall conform to each of the following requirements:
a) Ground rods shall be one–piece corrosion–resisting metal rods or pipes
(or equivalent in physical and electrical properties).
b) Ground rods shall not be less than 5/8 inch in diameter by 8 feet in
length.
c) Ground rods shall be driven into the ground so that one end of the ground
rod is at a minimum depth of 8 feet below the surface of the ground.
d) Pole–butt plates or wrappings shall not be used either in lieu of the
aforesaid ground rods, pipes, or as electrodes supplementary thereto.
e) On branch circuits extending from the grid, where return metallic paths
are not available, the driven ground rod(s), pipe(s), or equivalent shall
be located 24 inches or more from the surface of the pole. This 24 inches
clearance does not apply to the grounding conductor between ground rods.
f) Where two or more such rods are installed, they shall be located at
not less than 6 foot centers.
Note: Revised March 29, 1966 by Decision No. 70489; August
9, 1966 by Decision No. 71094; September 11, 1974 by Decision No. 83420;
November 6, 1992 by Resolution SU–15.
B. Neutral Conductors
(1) Locations: The common neutral grid system shall be grounded
at intervals not greater than 1,000 feet. On branch circuits extending
from a grid, where return loop paths are not available, the common neutral
conductor shall be grounded at intervals not greater than 500 feet.
For each transformer installed on a branch circuit without a loop return,
the transformer shall be so located that there will be one or more grounds,
of a combined resistance not greater than 3.5 ohms.
Note: Revised March 29, 1966 by Decision No.
70489; August 9, 1966 by Decision No. 71094; November 6, 1992 by Resolution
SU–15.
(2) Resistance: Where a common neutral system is used, the resistance
of the continuous metallic neutral grid to ground at any point shall not
exceed 3.5 ohms at any time.
EXCEPTION: If, after a definite effort has been made, it is found not
practicable to meet the above requirement, the following alternate requirement
will be accepted:
The resistance between any point of the continuous metallic neutral grid
and the ground connection at the substation shall normally not exceed 1
ohm. However, if the resistance exceeds 1 ohm, it shall be lower than
that of any individual ground connection on the grid, but in no case shall
it be greater than 2 ohms.
(3) Measurement of Resistance: Measurement of resistance by any suitable
method is recognized.
Note: Under the requirements
of Rule 59.4–B2, when the resistance exceeds 1 ohm but is to be less than
2 ohms, suitable ground rod connections (joints) and demonstrable calculations,
instead of neutral conductor resistance measurements, will be accepted.
C. Transformers
Ground conductors of transformers on common neutral systems shall conform
to the requirements of Rule 59.4–A1
.
On common neutral systems with transformers installed on a branch circuit
without a common neutral loop return, each transformer shall be so located
that there will be one or more grounds of a combined resistance not greater
than 3.5 ohms.
A transformer installation located on a grid section of a common neutral
system requires no independent ground provided there is a ground connection,
having a resistance not in excess of 3.5 ohms, to the common neutral conductor
either at the transformer pole or at an adjacent pole.
Note: Revised March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094; November 6, 1992 by Resolution SU–15.