General Order 95
  
Section VII
  
Detailed Construction Requirements for Trolley and Electric Railway
  Contact and Feeder Conductors and Their Supporting Messengers,
  Span Wires, Etc. (Class T Circuits)
  
74.4    Clearances
           
Except where specifically designated, Class T conductors take
   clearances specified for supply lines of like voltage.
        
    
A.    Above Ground
The minimum vertical clearances above ground for Class T
conductors shall be those specified in Rule
37
   , Table 1
   . References to rules modifying the tabulated values for supply conductors 
 and Class T conductors of equal voltage are given in notes following 
   Table 1
   .
            
    
    
B.    Above Railways
            
                        
    
(1) Tracks: The vertical clearance of 22.5 feet above rails for trolley contact, feeder and span wires of Table 1, Case 2, Column C, may be decreased to 19 feet where the railway involved does not transport nor proposes to transport freight cars.
Note:    
  Revised February 1, 1948 by  Supplement  No. 1 (Decision No. 41134, Case
 No. 4324) and Revised January 13, 2006 by Decision No. 05-01-030
                                                                        
          
            
    (2)    At Grade Crossings of Railroads: Unless  electric railroad systems
  are protected by interlocking plant at grade crossings  with interurban
or  other heavy or high speed railway systems, the trolley  contact conductors
  shall be at the same elevation above their own tracks throughout the crossing
  and next adjoining spans. In addition to the above, catenary construction
  shall be provided when crossing spans exceed 100 feet (see 
     Figure 74–2
      ). This rule is not intended to apply where pantograph collector or 
similar   device is used.
                              
Note:    Revised October 9, 1996
  by  Resolution SU–40.
                                                                        
                                  
                
C.    Between Conductors
                      
                                            
    
The minimum clearances specified in 
   Case 2, Column D; Case 4, Column B; Case 5, Column E and Case 15, Column 
 D of Table 2
    are not required between Class T conductors of the same potential and 
system.
                            
        
        
The minimum clearance of 24 inches specified
   in Table 2, Case 9, Column 
 D
   , is not required between trolley feeders of the same system provided, 
however,  that the clearance shall be not less than 12 inches.
The minimum clearance of 48 inches
   specified in Table 2, Case 
 2, Column D, and Case 4, Column B
    is not required  in double trolley construction between feeder auxiliary 
 span cables or equalizer  cables and trolley contact conductors of opposite 
 polarity provided, however,  that the clearance shall be not less than 18 
 inches or, where the feeder or equalizer cables are attached to the span 
wires in accordance with Rule 74.4–G3
   , the clearance shall be not less then 3 inches at the point of crossing
 the trolley contact conductor.
                                    
        
        
Trolley contact conductors of
   the same system but of opposite polarity, (as in double trolley construction)
   or of different systems and of the same or opposite polarity, shall have
  a separation of not less than 11–1/2 inches. Excepted from this provision
  are conductors at switches, frogs, crossings, etc., in which locations
a  vertical separation of not less than 3 inches shall be maintained between
 conductors of opposite polarity.
                                        
        
D.    From
   Poles
                                        
                                                                                
    
Class T conductors of not
   more than 750 volts and of the same polarity, potential and system which
  are carried on poles supporting no other conductors are not required to
obtain   the clearance of 15 inches from center line of pole (
   Table 1, Case 8
   ), but  shall comply with the clearance of 3 inches from surface of pole 
 (Table 1,  Case 9
   ). The attachment of clearance arms for either supply or communication 
 service drops does not affect the pole clearance of Class T conductors which
  are carried on one side or the top of a pole.
                                              
        
        
Where Class T conductors
   are carried on more than one side of jointly occupied poles the clearances
   of Table 1, Cases 8 and 9
   , shall apply and a climbing space conforming to  
   Rule 54.7
    shall be provided.
                                                  
        
        
Class T conductors
   of not more than 750 volts passing unattached shall clear nonclimbable
street   lighting and traffic signal poles, or standards, including mastarms,
brackets,   and lighting fixtures; a radial distance of 15 inches as specified
in   Table  1, Case 10, Column
C
   ; except when the conductors are mechanically protected  from abrasion 
by  materials specified in Rule 22.8
   . Such mechanical protection  shall extend 15 inches in each direction 
along  the cable from centerline of pole, standard, attaching mastarms, or 
fixtures;  whether passing above, below or alongside. The conductors shall 
be installed  in such a manner so as not to interfere with light distribution 
from lighting  fixtures and shall not hamper workmen changing lamps or maintaining 
equipment.
                                                      
        
Note:   
   Modified January 8, 1980 by Decision No. 91186.
                                                                        
                                                                        
                                                                        
                                                                        
       
                                                
E.   
   Under Bridges, Etc.
                                                      
                                                                                                            
    
A reduction
   of the clearances given in Table 1
    to a minimum of 14 feet for trolley contact  conductors is permitted
for  subways, tunnels or bridges, and for 0 - 750 volt conductors within
exclusive  and semi–exclusive rights–of–way as defined by Alignment Classification 
9.04–a.  and 9.04–b.(1) contained in General Order 
 No.  143–A
   , “Safety Rules and Regulations Governing Light–Rail Transit”, provided
  the railway does not operate freight cars where the vertical distance from 
  the top of car or load to trolley contact conductor is less than 6 feet. 
 This will require the grading of the trolley contact conductor from the prescribed
  construction down to the reduced elevation (see 
      Figure 74–1
      ).
                                                            
        
        
No clearance
   is specified between the trolley contact conductor and the structure.
Where    the structure is of material which will ground the trolley current
in the    event the collector leaves the contact conductor, a properly insulated
trolley   trough or equivalent protection shall be installed to prevent contact
between   the collector and the structure. Where pantograph collectors are
used, this   protection is not required. See 
 Rule 54.4–I
    for provisions applicable to conductors other than trolley contact conductors.
                                                                
        
Note:   
   Modified June 27, 1978 by Decision No. 89022; and January 21, 1992 by
Resolution    SU–10.
                                                                        
                                                                        
                                                                        
                                                                        
                                                                   
                                                          
      
    
F.    At Points of Failure
                                                                
                                                                                                                                    
      (1)    Overhead Trolley Contact Conductors: All overhead trolley contact
   conductors shall be so supported and arranged that the breaking of a single
   “suspension” or fastening will not allow the trolley conductor, or live
 span  wire, or current carrying connections to come within 10 feet from
the  ground  or from any platform accessible to the general public. This
does not apply  to feeder taps to or from trolley contact conductors (see
Appendix  G, Figs.  
        65
    and 66
   ).
                                                                      
        
        
      (2)    Trolley Contact Conductors of More than 1,500 Volts: Where
in  urban  districts and not on fenced rights–of–way, trolley contact conductors 
 of more than 1,500 volts shall be so suspended that if the conductor is broken
 at a single point it cannot fall within 10 feet from the ground or from
any  platform accessible to the general public. This practically requires
 catenary  construction.
                                                                        
                                                                     
        
G.    From Span Wires, Guys and Messengers
                                                                        
                                                                       
                                                                        
                                                                        
                                                                                                                                              
    
The minimum clearances of conductors from span wires, guys and messengers
   are specified in Table 2
    and are modified for Class T conductors by the following  rules and by
                                                                        
    Rule 78
   .
                                                                        
       
        
        
(1)    Span Wires and Contact Conductors: The minimum clearance of 
48 inches   specified in Table 
2, Case  1, Column B, and Case 2, Column A
   , is not required  between span wires and trolley contact conductors supported 
 therefrom.
                                                                        
           
        
      (2)    Trolley Contact Conductors of 750 - 7,500 Volts: The clearance
  specified  in Table 2, Case 
 1, Column E, and Case 5, Column A
   , shall be increased to  not less than 48 inches where trolley contact 
conductors  of 750 - 7,500 volts  are involved. These clearances are not intended
to apply to span wires and  trolley contact conductors supported therefrom.
                                                                        
               
        
      (3)    Feeder and Equalizer Cables: Feeder auxiliary span cables or
 equalizer   cables shall be installed at a distance not less than 18 inches
 above the   span wire (see 
  Appendix G, Figure 67
   ), or in lieu thereof, such cables, when  protected by the equivalent
of  triple–braid weatherproof covering, may be  supported not less than 2–1/2 
 inches above the span wire by insulating supports  attached to the span wire
 at intervals of not more than 5 feet.