Original Version
Rule 54.4-D6c
    
54.4-D6c)    New Rule
Strikeout and Underline Version
Rule 54.4-D6c
    
54.4-D6c)    More than 750 Volts supported on non-climbable
poles: Where conductors : are dead-ended on a non-climbable pole in partial
underground distribution, the energized portions of such conductors shall
be not less than 6 inches from surface of pole (see Rule 54.4-D2).
  
  Final Version
Rule 54.4-D6c
  
54.4-D6c)    More than 750 Volts supported on non-climbable
poles: Where conductors : are dead-ended on a non-climbable pole in partial
underground distribution, the energized portions of such conductors shall
be not less than 6 inches from surface of pole (see Rule 54.4-D2).