Original Version
Rule 44.2
44.2 Replacement
Lines or parts thereof shall be replaced or reinforced before safety factors have been reduced (due to deterioration or changes in construction arrangement or other conditions subsequent to installation) in Grades “A” and “B” construction to less than two-thirds of the construction safety factors specified in Rule 44.1 and in Grades “C” and “F” construction to less than one-half of the construction safety factors specified in Rule 44.1. Poles in Grade “F” construction shall also conform to the requirements of Rule 81.3-A.
In no case shall the application of this rule to Grades “A”, “B” or “C” construction or to guys in Grade “F” construction be held to permit the use of structures or any member of any structure with a safety factor less than one.
Strikeout and Underline Version
Rule 44.2
44.2 Replacement
Lines
or parts thereof shall be replaced or reinforced before safety factors have
been reduced (due to deterioration or changes in construction arrangement or
other conditions subsequent to installation) in Grades “A” and “B”
construction to less than two-thirds of the construction safety factors
specified in Rule 44.1 and in Grades “C” and “F” construction to less than
one-half of the construction safety factors specified in Rule 44.1. Poles in
Grade “F” construction shall also conform to the requirements of Rule 81.3-A.
In
no case shall the application of this rule to Grades “A”, “B” or “C”
construction or to guys in Grade “F” construction be held to permit the use
of structures or any member of any structure with a safety factor less than
one.
Final Version
Rule 44.2
44.2 Replacement
Lines or parts thereof shall be replaced or reinforced before safety factors have been reduced (due to deterioration) in Grades “A” and “B” construction to less than two-thirds of the construction safety factors specified in Rule 44.1 and in Grades “C” and “F” construction to less than one-half of the construction safety factors specified in Rule 44.1. Poles in Grade “F” construction shall also conform to the requirements of Rule 81.3-A.
In no case shall the application of this rule be held to permit the use of structures or any member of any structure with a safety factor less than one.