Previous Rule Change | Main Page | Resolution Decision Main Page | Change List for this Rule | Search Decision Number 14-02-015 | Decision Number 14-02-015 | Next Rule Change |
Original Version
Rule 54.10-H
54.10-H. | Fastenings |
Hardware used in connection with messengers shall meet the strength requirement of Rule 49.7–C . Deadend attachments used on messengers shall have a strength not less than that of the messenger. Where cables are not maintained by workers using a cable chair, the additional allowance of 200 pounds vertical load, specified in Rule 49.7–C may be reduced to 50 pounds to allow for the load imposed by workmen on ladders. |
Strikeout and Underline Version
Rule 54.10-H
54.10-H. | Fastenings |
Hardware used in connection with messengers shall meet the strength requirement of Rule 49.7–C. Deadend attachments used on messengers shall have a strength not less than that of the messenger. Where cables are not maintained by workers using a cable chair, the additional allowance of 200 pounds 300 lbs.. vertical load, specified in Rule 49.7–C may be reduced to 50 pounds 75 lbs. to allow for the load imposed by workers workmen on ladders. |
Final Version
Rule 54.10-H
54.10-H. | Fastenings |
Hardware used in connection with messengers shall meet the strength requirement of Rule 49.7–C. Deadend attachments used on messengers shall have a strength not less than that of the messenger. Where cables are not maintained by workers using a cable chair, the additional allowance of 300 lbs. vertical load, specified in Rule 49.7–C may be reduced to 75 lbs. to allow for the load imposed by workers on ladders. |